NORMALLY
OPEN
UNLOADING
SOLENOID
SUCTION
SOLENOID
LOADING
NORMALLY
CLOSED
SCHRADER VALVE
CHECK
SERVICE
SUCTION
VALVE
'B'
'A'
VALVE
BOX
TERMINAL
3.0 OPERATION
When the compressor is given a "hold"
command, valve A is de-energized (closed) and
slide valve movement is halted. The internal
pressure regulating valve allows oil to bleed from
the slide valve chamber during the hold
condition. If valve B is then de-energized (open),
the high pressure oil acting on the slide valve
will be vented to suction, and the pressure in the
slide valve chamber will be reduced. The slide
valve spring will now move the slide valve back
toward the minimum capacity position.
Under standard conditions, the compressor will
load in 60 seconds and unload in 55 seconds.
SLIDE VALVE POSITION
UNLOADING
LOADING
HOLD
SOLENOID VALVE A
(NORMALLY CLOSED)
CLOSED
(DE-ENERGIZED)
OPEN
(ENERGIZED)
CLOSED
(DE-ENERGIZED)
SOLENOID VALVE B
(NORMALLY OPENED)
OPEN
(DE-ENERGIZED)
CLOSED
(ENERGIZED)
CLOSED
(ENERGIZED)
FIGURE 3.13
COMPRESSOR CAPACITY CONTROL DETAIL
- 18 -
Содержание ACXi 165-5SP-LN
Страница 6: ...2 0 INSTALLATION FIGURE 2 3 2 ACXi 165 5SP LN TYPICAL RIGGING 6...
Страница 9: ...2 0 INSTALLATION FIGURE 2 4 2 ACXi 165 5SP LN DIMENSIONAL DATA NOTE ALL DIMENSIONS ARE IN INCHES MM 9...
Страница 14: ...3 0 OPERATION FIGURE 3 2 ACXi 165 5SP LN TYPICAL SCHEMATIC PIPING 14...
Страница 20: ...CHECKED REV NO DATE APPROV 4 0 ELECTRICAL FIGURE 4 2 ACXi 165 5SP LN WIRING SCHEMATIC 20...
Страница 21: ...4 0 ELECTRICAL 21...
Страница 22: ...4 0 ELECTRICAL 22...
Страница 23: ...4 0 ELECTRICAL 23...
Страница 24: ...4 0 ELECTRICAL 24...
Страница 25: ...4 0 ELECTRICAL 25...
Страница 26: ...4 0 ELECTRICAL 26...
Страница 27: ...4 0 ELECTRICAL 27...
Страница 28: ...4 0 ELECTRICAL 28...
Страница 29: ...4 0 ELECTRICAL 29...
Страница 30: ...4 0 ELECTRICAL 30...
Страница 31: ...4 0 ELECTRICAL 31...