background image

ELECTRICAL CONNECTIONS

 

All units are wired as completely as possible at the factory
prior to delivery.  The connections which must be made by
the installer are to the main power source, control power
source, separate chiller heater power source and
interlocking the satellite equipment.  In connecting power
wiring to the unit, the following precautions should be taken:

!

 All field wiring is to be in accordance with the National

Electrical Code and state and local codes.

!

 All wiring is to be checked for damage and all terminal

connections tested for tightness.  Unit terminal blocks are
to be connected with copper conductors only, sized per
ampacity listed on unit data plate.

!

 The power supply should match the unit nameplate in

volts, phase and Hertz.  Voltage must be within ± 10% of
nameplate value and voltage imbalance between phases
must not exceed 2%.

!

 For minimum circuit ampacity and maximum fuse size,

see Unit Nameplate.

Two separate 115 volt power sources must be field supplied
to provide power for control and heater circuits.  If optional
control circuit transformer is provided, only one separate 15
Amp, 115V power source is required for chiller heater circuit.
All electrical connections should be periodically tightened.

Refer to the unit nameplate data for the minimum circuit
ampacity and maximum allowable dual element fuse size.
The factory supplied field power block is sized to accept
wires sized per NEC, 75C (3-in-conduit) up to 500MCM as
required.  When multiple wires per pole are required to stay
at or below 500MCM, the power block supplied will have
multiple wire per pole capability.

A separate 15 amp 115V field power supply is required to
power the main control circuit (which includes the
compressor sump heaters) unless the control transformer
option is included.  

OPERATION - ACDX

GENERAL

work involved, and also to be trained in the operation and

The unit should be started up only by a refrigeration
technician who is familiar with accepted operation practices

The representative will inspect the installation to

for refrigeration systems.

determine whether it meets Dunham-Bush, Inc.

Use small screw unit start-up report, Form NS1157 to record

installation, determine whether it is in satisfactory

all temperature, pressure, electrical readings and control

operating condition, and instruct specified customer

settings.  A copy must be forwarded to Dunham-Bush, Inc.,

personnel in its operation and maintenance for the length

North American Service, Harrisonburg, Virginia before the

of time specified in the purchase contract.

warranty will be honored.

AIR COOLED PACKAGE CHILLER START-UP - ACDX

of 24 hours and the oil sump temperature must be at a

The unit is ready for start-up when the following procedures

representative.  This will ensure that the oil is warm

have been completed.  

enough to vaporize any dissolved refrigerant and that the

1. Water piping for the cooler is installed and tested.
2. Electrical connections are made and properly fused.

2. Before starting the compressor(s), check all three phases

3. Unit has been leak tested, leaks corrected, and charge

of supply voltage, of all legs of the motor.  They must be

completed.

within ± 10% of the nameplate voltage.  Check to be sure

4. Compressor crankcase heater(s) has been energized for

compressor is not running backwards.

a minimum of 24 hours.

5. Calibrated refrigerant gages have been connected to the

3. Start compressor(s), check the gages and note if the

suction and discharge.

pressures are within the prescribed limits.

6. Turn on the chilled water pump, check direction of

rotation and adjust the water flow through the cooler to

4. Check the refrigerant sight glass at the TX Valve to be

the specified flow rate.  Bleed off all entrained air.

sure it is free of bubbles.  If not, charge as required to

7. Manually energize the fan starters and check the fan

clean sight glass.               .

rotation.  Fans should pull air through the condenser coil
and discharge vertically upwards.  

5. Stage unit down until all compressors are off and check

8. Check all refrigerant valves to be sure they are open.

the compressor crankcase sight glass for oil level.  It

9. Proceed to System Start-up.

should be 1/2 to 3/4 of the compressor sight glass.  If not,

SYSTEM START UP

1. Request for Start-Up Representative - Start-up service is

expansion valve superheat setting should be checked, it

an option for these units and is requested when the unit

should be between 9

E

 and 12

E

F at full load design

is ordered.  If you purchased start-up service, then after

conditions.  In some instances, it will be necessary to

the installation has been completed and checked, Form

lower the superheat setting to ensure proper distribution.

9180 must be filled out and sent to the local Dunham-

Turn the TX valve adjustment stem clockwise to increase

Bush representative who sold the unit.  Following receipt

the superheat setting and counterclockwise to decrease

of this signed form, a representative will be sent to the

the setting.  Be sure and allow ample time between each

customer.  The purchaser should have competent service

adjustment for the system to rebalance.

and operating personnel in attendance to assist in the

maintenance of this unit.

requirements, perform the initial start-up of the

NOTE:  Sump oil heaters should be energized a minimum

minimum of 100

E

F (38

E

C) prior to arrival of start-up

oil is within the normal operating temperature range.

see procedure for adding oil on page 7.

6. Restart the compressor.  After an hour of operation, the

6

Содержание ACDX

Страница 1: ...ctions 6 ACDX Operation Start up 6 7 Maintenance 7 Slide Valve Unloading Operation 8 Low Ambient Operation 9 Fan Position Numbers 10 Fan Cycling Sequence 11 ACDX Sequence of Operation 12 Electrical Co...

Страница 2: ...rs attention to the instructions contained herein it will give To use this manual effectively you must first identify your unit model from the unit nameplate It is assumed the user of this manual and...

Страница 3: ...eration Weight 3592 4732 5044 7712 9684 10726 MODEL SIZE 150 170 185 210 235 255 Compressor Model Qty SSCA060 3 SSCA075 3 SSCA060 4 SSCA075 4 SSCA060 1 SSCA060 2 SSCA075 2 SSCA075 2 Displ CFH Compr 72...

Страница 4: ...cables or other moving equipment are placed so as to avoid damage to the unit or piping The refrigerant Under certain critical conditions it may be necessary to piping must not be used as a ladder or...

Страница 5: ...microcomputer controlled units conjunction with a spring loaded bypass regulating valve as shown in Figure 1B The bypass valve must be set to Water Quality ACDX Coolers used in these packages are ass...

Страница 6: ...5 TYPICAL CHILLED WATER PIPING TYPICAL MULTIPLE PACKAGED CHILLED WATER CONNECTIONS PARALLEL FLOW PARALLEL FLOW SERIES FLOW...

Страница 7: ...ump temperature must be at a The unit is ready for start up when the following procedures representative This will ensure that the oil is warm have been completed enough to vaporize any dissolved refr...

Страница 8: ...Compressor Models SSCB use DB Karlube 21 Oil Contact factory for price The above listed oils are synthetic lubricants of the Polyol Ester POE type Due to the complex nature of the POE great precaution...

Страница 9: ...en or close UL 1 and UL 2 in response to the supply water temperature The slide valve will move to the left loading by force of discharge pressure whenever UL 1 opens to permit flow to the oil return...

Страница 10: ...ell as that portion of the surface rejecting heat by natural convection with related fans off To further assist low ambient starts all fans are held off until the head pressure reaches 190 psig This a...

Страница 11: ...C1 1 3 5 7 9 11 C2 2 4 6 8 10 12 150 1 2 150 3 C1 1 3 5 7 9 11 13 15 C3 C2 2 4 6 8 10 12 14 16 Front Rear 170 1 2 170 3 185 1 2 185 3 C1 1 3 5 7 9 11 13 15 17 C3 C2 2 4 6 8 10 12 14 16 18 Front Rear...

Страница 12: ...1 RH 2 4 6 8 10 12 1 LH 1 3 5 7 9 11 2 LH RH 13 14 15 16 17 18 Rear Module 185 1 RH 2 4 6 8 10 12 1 LH 1 3 5 7 9 11 2 LH RH 13 14 15 16 17 18 Rear Module 210 1 LH 1 3 5 7 9 Rear Module 1 RH 2 4 6 8 1...

Страница 13: ...M1 1 opens to de energize oil light is not on disconnect the main power and reverse sump heater 1HTR and switch 1M1 2 closes to any two phase legs at the Main Incoming Power activate the fan control c...

Страница 14: ...ed Compressor No 2 will not be able to restart for five minutes due to integral time delays SAFETY CONTROLS The unit is protected by the following safety controls 8 Water Flow Switch FLS 1 High Pressu...

Страница 15: ...occurs temperature during the compressor off when ambient temperature is below 40EF cycle preventing refrigerant migration in 3TAS is measuring ambient temperature to the crankcase and consequent and...

Страница 16: ...ges 27 1TAS Motor Overload Protection Compressor overload protection is 1 Unit Control Contact Unit on off control should be provided by a solid state device 1TAS done through the terminals shown on t...

Страница 17: ...ps Electrically Programmable Read Only an NC25 microcomputer system The computer Memory store general operating procedures system is composed of a main microcomputer algorithms and is the same for all...

Страница 18: ...nce midnight and the accumulated run time during yesterdays Y twenty four hour period CYC gives the number of times that the control point cycled off since midnight If a feedback digital input is asso...

Страница 19: ...then new calibration would be 58 60 3 1 3 3 3 So the zero calibration should be changed to 3 1 You must be authorized See Section 3 4 2 Select DATE TIME SET on the main menu Press ENTER to display cur...

Страница 20: ...r start delay 7 Power loss reset 8 Anti recycle timing 9 Low pressure safety 19 11 Freeze safety 12 High Oil Temp Safety 13 Alarm Output 14 Fan control 15 Chilled water reset and customer control inte...

Страница 21: ...rough 4 for each compressor number manual control DO NOT start a compressor 7 Add the value obtained in step 5 to the amps calculation A setpoint value from step 6 NOTE All compressors will revert bac...

Страница 22: ...rator pressure of a given Sample Ramp Times Minutes For a Two pressure B setpoint a time delay is initiated If Compressor Unit with a 2 Second Compressor the pressure stays below the setpoint during t...

Страница 23: ...ow normal compressor control if the unit schedule is calling for unit operation that a compressor auxiliary contact digital input stays ON for 15 seconds when the computer is commanding the compressor...

Страница 24: ...e pressed after the problem is resolved HOLD state If the discharge pressure 4 23 Low Chiller Flow Alarm A low flow alarm will be generated if a compressor control point is ON and the flow switch digi...

Страница 25: ...TYPICAL POWER WIRING ACDX120A...

Страница 26: ...TYPICAL CONTROL WIRING ACDX120A...

Страница 27: ...TYPICAL OPTIONS WIRING ACDX120A...

Страница 28: ...TYPICAL CONTROL WIRING ACDX120B W MICRO...

Страница 29: ...TYPICAL CONTROL WIRING ACDX120B W MICRO...

Страница 30: ...TYPICAL OPTIONS WIRING ACDX120B W MICRO...

Страница 31: ...5 472 12 1 5 5 9 400 3 4 1120 9 3 460 257 350 75 2 98 539 180 12 1 5 3 0 400 3 4 1120 9 3 150 230 570 700 60 3 152 1228 409 16 1 5 5 9 600 5 0 1120 9 3 208 632 800 60 3 171 1228 409 16 1 5 5 9 600 5 0...

Страница 32: ...Cooler Model Curve No Min GPM Max GPM 040 CHSO10601B 1 78 315 050 CHS011601B 1 86 315 060 CHS013601B 2 101 420 080 EXD14102J09 3 140 440 095 EXD16112J09 4 175 519 120 EXD16122J07 5 236 697 150 EXT181...

Страница 33: ......

Страница 34: ...ACDX AUDX CONDENSER CLEARANCE...

Страница 35: ......

Страница 36: ...ACDX LOAD POINTS...

Страница 37: ...ACDX RUBBER IN SHEAR ISOLATOR...

Страница 38: ...ACDX SPRING ISOLATOR...

Страница 39: ...AUDX LOAD POINTS...

Страница 40: ...AUDX RUBBER IN SHEAR ISOLATOR...

Страница 41: ...AUDX SPRING ISOLATOR...

Страница 42: ...4 Clean the condenser 5 Compressor discharge check valve not operating 5 Replace if necessary properly 6 Fans not running 6 Check pressure control setting condenser pressure exceeds saturated pressure...

Страница 43: ...Start Up a Open compressor discharge service valve if supplied b Open liquid valve s c Open suction and discharge valves to pressure gauges if supplied d Check rotation of all fan motors e Start auxi...

Страница 44: ...101 Burgess Road Harrisonburg VA 22801 PH 540 434 0711 FAX 540 434 4595 Printed in U S A I O 6193A Issued 9 98...

Отзывы: