FLOW CURVE
Valve
SV 1005 / 1007
SV 1005 / 1007
SV 1010 / 1012
SV 1010 / 1012
SV 1010 / 1012
SV 1010 / 1012
SV 1015 / 1020
SV 1015 / 1020
SV 1015 / 1020
SV 1015 / 1020
Pipe Size
1/2
3/4
1/2
3/4
1
1 1/4
1
1 1/4
1 1/2
2
Part # NPT
Flange Kit*
242-650
242-651
242-653
242-654
242-655
242-656
242-657
242-658
242-659
242-660
Part # Rp
Flange Kit*
242-220
242-221
242-223
242-224
242-225
242-226
242-227
242-228
242-229
242-230
R e p l a c e m e n t
Coil (120Vac)
246-502
246-502
246-503
246-503
246-503
246-503
246-504
246-504
246-504
246-504
Spec. gravity of Natural Gas
Spec. gravity of gas used
f =
V
gas used
=
°
V
Natural Gas
x f
°
Type of gas used
Natural gas
Butane
Propane
Air
Density
[kg/m
3
]
0.81
2.39
1.86
1.24
sg
0.65
1.95
1.50
1.00
f
1.00
0.58
0.66
0.80
To determine the pressure drop when using a gas other than natural gas, use the flow formula below and f value located
in the chart below to determine the “corrected” flow rate in CFH through the valve for the other gas used. For example,
when using propane, divide the volume (CFH) of propane required for the application by the calculated value f (f = 0.66 for
propane). Use this “corrected” flow rate and the flow curve above to determine pressure drop for propane.
Use this formula to calculator the f factor for
other gases not listed on the table.
PRESSURE DROP FOR OTHER GASES
REPLACEMENT PARTS
* Mounting kit includes 1 flange, 4 bolts and 1 O-ring.
Electrical
Plug
(Hirschmann)
210-319
M20-1/2” NPT
adapter
240-671
Valve Indicator
217-665
Part #
PCB Board
245-147
245-147
245-153
245-153
245-153
245-153
245-153
245-153
245-153
245-153