Dungs SV-DLE 1005/604 Скачать руководство пользователя страница 2

2 … 6

2 … 6

Recommended Preparation

• Examine the SV-(DLE) for shipping damage.
• The main gas supply must be shut off before   
   installing the valve.
• The inside of the SV-(DLE), the flange, and piping 
   must be clean and free of dirt and debris before installing. 
   Failure to remove dirt and debris could result in valve 
   damage and/or improper performance.

Flange Mounting Procedure

• Verify that the o-ring and the groove is clean and in 
   good condition on the outlet side of the valve.
• Install the SV-(DLE) with the gas flow matching the 
   direction indicated by the arrows on the casting.
• Mount the SV-(DLE) with the solenoid vertical upright to  
   horizontal.
• Clean the mounting surface of the flange.
• Attach the flange to the outlet of the SV-(DLE) using the 
   screws supplied.
• Use a 4mm Allen wrench for the M5 screw. 
 

SV / SV-DLE1005 & 1007

• Use a 5mm Allen wrench for the M6 screw.  
 

SV / SV-DLE 1010, 1012

• Use a 6mm Allen wrench for the M8 screw. 
    

SV / SV-DLE 1015, 1020

• Tighten the screws in a crisscross pattern
• Do not overtighten the screws. Follow the maximum 
   torque values below.

Recommended Torque
 

M5 

M6 

M8 

Screw Size

 

44 

62 

134 

[lb-in]

Recommended Piping Procedure

• Use new, properly reamed and threaded pipe.
• Apply good quality pipe sealant, putting a moderate  
   amount on the male threads only. If pipe sealant lodges 
   on the valve seat, it will prevent proper operation. If using 
   LP gas, use pipe sealant rated for use with LP gas.
• Do not thread pipe too far. Valve distortion and/or mal-
   function may result from excess pipe in the valve body.
• Apply counter pressure with a parallel jaw wrench only to 
   the flats on the flange when connecting to pipe.
• Do not overtighten the pipe. Follow the maximum torque 
    values listed below.

Recommended Torque for Gas Piping
1/2”   3/4”   1”  

1-1/4”  1-1/2”  2”   

NPT pipe

375 

560 

750 

875 

940 

1190   [Ib-in]

• After installation, perform a complete leak test using a 
soapy solution. The presence of bubbles indicates a leak.

MOUNTING

If the flow is not in the same direction of the arrows 
on the valve body, the valve will not 
operate properly.

PAINTING VALVE

It is not recommended that this valve be painted. Paint-

• 

ing covers date codes and other labels that identify this 
valve.
If the valve needs to be painted, a paint free of volitile 

• 

organic componants (VOC’s) must be used.  VOC’s can 
damage valve o-rings, resulting in external gas leakage 
over time.

During the painting process, use measures that will allow 

• 

the valve’s date code and other labeling information to be 
legible after the paint is dry.

PROTECTION FROM RADIANT HEAT

Radiant heat must be considered as a heat source that 

• 

could result in an ambient temperature higher than the 
rating of this valve.

Provide propor shielding to protect against radiant heat.

• 