Dungs SV-DLE 1005/604 Скачать руководство пользователя страница 5

4 … 6

4 … 6

5 … 6

 VALVE LEAKAGE TEST

This leak test procedure tests the external sealing and valve 
seat sealing capabilities of two SV automatic safety shutoff 
valves in series.  Only qualified personnel should perform this 
test. 

It is required that this test be done on the initial system start-
up, and then repeated at least annually.  Possibly more often 
depending on the application, environmental parameters, and 
the requirements of the authority having jurisdiction.   

SETUP

This test requires the following:
A) Test nipples installed in the downstream pressure tap 
    port of each automatic safety shutoff valve to make 
    the required 1/4” hose connection in step 4.
B) A transparent glass of water filled at least 1 inch from 
    the bottom.  
C) A proper leak test tube.  An aluminum or copper 1/4” 
    rigid tube with a 45˚ cut at the end that is then connected 
    to a 1/4” flexible hose of some convenient length pro-
    vides for a more accurate leakage measurement.  
    However, a 45˚ cut at the end of the 1/4” flexible hose will 
    suffice, but it will not likely be as accurate as the rigid 
    tube.  
D) For detecting external leakages, an all purpose liquid leak 
    detector solution or a soapy water solution is required. 

LEAK TEST PROCEDURE 

Use the illustration below as a reference.
1. With the upstream ball valve open, the downstream ball 
    valve closed and both valves energized, apply an all pur-
    pose liquid leak detector solution to the “External Leakage 
    Test Areas” indicated in the illustration below, to any 
    accessories mounted to the safety valve, and to all gas 
    piping and gas components downstream the equipment 

    isolation valve, and the inlet and outlet gas piping for each 
    automatic safety shutoff valve. The presence of bubbles 
    indicates a leak, which needs to be rectified before 
    proceeding. 
2. Then, de-energize the burner system and verify that both 
    automatic safety shutoff valves are closed. 
3. Close the upstream and downstream manual ball valve.
4. Open the downstream test nipple of the upstream 
    valve, and connect the 1/4” flexible hose to the test nipple.
5. Slowly open the upstream manual ball valve, and then  
    provide for some time to allow potential leakage to charge 
    the test chamber before measuring the valve seat leakage.
6. Immerse the 1/4 in. tube vertically 1/2 in. (12.7 mm) below 
    the water surface. If bubbles emerge from the 1/4” tube
    and after the leakage rate has stabilized, count the 
    number of bubbles appearing during a 10 second period. 
    (See chart below for allowable leakage rates.)
7. Repeat the procedure for the downstream automatic  
    safety shutoff valve except that valve #1 needs to be 
    opened during the leakage test.

After completing the above tests proceed as
follows: 

8.   Verify that the downstream manual ball valve is
      closed, and both automatic safety shutoff valves are
      de-energized. 
9.   Remove the flexible hose, and close all test nipples. 
10. With the upstream manual ball valve open, energize 
      both automatic safety shutoff valves.
11. Use soapy water to leak test all test nipples to ensure 
      that there are no leaks.
12. If no leakage is detected, de-energize all automatic 
      safety shutoff valves, and open the downstream manual 
      ball valve.

Valve Type                Allowable Valve Seat Leakage*  

 

# of Bubbles in 10 Sec.

                                       

for up to 10 PSI inlet  

  

 

AIR 

Natural Gas  LP

SV-(DLE) 1005/1007 

 

239cc/hr  

  

 

       6 

 

SV-(DLE) 1010/1012 

 

464 cc/hr  

 

 

       11   

7

SV-(DLE) 1015/1020 

 

588 cc/hr  

 

 

10 

       12   

8

*Based on air, and test conditions per UL 429 Section 29. (Air or inert gas at a pressure of 1/4 psig and also at a pressure of one and one-half 
times maximum operating pressure differential, but not less than 1/2 psig. This test shall be applied with the valve installed in its intended posi-
tion.)  Volume of bubble defined in Table 2 of FCI 70-2-1998.

SV-(DLE): 1010, 1012, 1015, 1020

SV-(DLE): 1005, 1007

(see step 1)

WARNING: If leakage values are 
exceeded, replace valve immediately. 

NOTE: The position of the side taps #2 
and #3 on the SV 1005/1007 are not the 
same as on the SV 1010-1020 valves.

Отзывы: