Electrical Connection

 DlN-Connector with 1/2” NPT conduit adapter.

Operating Time 

 

 

 

 

 

 100 % duty cycle

Closing Time

 < 1 second

Opening Time

 SV/604: < 1 sec.
 SV-DLE/604: 10 to 20 sec. (70 °F)

Max. Flow Adjustment (SV-DLE/604)

 Adjustable: 0 to 100 % of total flow. When adjusted to low 
 flows, flow repeatability upon opening is +/-15%.  

Initial Lift Adjustment (SV-DLE/604)

 Adjustable: 0 to 70 % of total flow; 0 to 35% of stroke

Materials in contact with Gas 

 

 

 Housing: Aluminum & Steel, free of non-ferrous metals
 Sealings on valve seats: NBR-based rubber

Mounting Position

 Solenoid upright vertical
 to solenoid horizontal 

Strainer

 23 Mesh, installed in the housing upstream valve seat

Test Ports

 G 1/8 ISO 228 taps available on both sides upstream and  
 downstream of valve seat, on inlet and outlet of SV also on  
 flange (SV 1010-1020 only). See Page 4 for details. 

        

Approvals 

 CSA: Certified File No.1350312
 FM Approved: Report 3014562

 Commonwealth of Massachusetts Approved Product

 Approval code G1-1107-35

SV-(DLE) 10../604
Safety Shutoff Valve
Installation Instructions 

SPECIFICATIONS

SV/604  

Normally closed automatic shutoff valve with proof of closure. Fast opening, fast closing.

SV-DLE/604

 

   Normally closed automatic shutoff valve with proof of closure. Slow opening, fast closing. Valve features  

 

 

 

adjustable max. flow and adjustable inital lift.

SV/604 Installation Manual - P/N 80144 - Ed. 01/09

Body size 

 

   Size (NPT) 

 

 

       

 SV / SV-DLE 1005/604     1/2”
 SV / SV-DLE 1007/604     3/4”
 SV / SV-DLE 1010/604     1”
 SV / SV-DLE 1012/604     1 1/4”
 SV / SV-DLE 1015/604     1 1/2”
 SV / SV-DLE 1020/604     2”

Gases  

 Natural gas, propane, butane; other noncorrosive gases.
 When used with manufactured gases, quarterly leak     
 checks are required. Suitable for dry, 0.1% by volume H

2

S.

Maximum Operating Pressure 

 

 

      

 10 PSI (700 mbar)

Maximum Close Off Pressure

 

 15 PSI (1000 mbar)

Ambient / Fluid Temperature 

 

 

           

 -40°F to +140°F; (-40°C to +60°C)     

Electrical Ratings Available 

 

 

 

 120 Vac - 50 to 60 Hz

Enclosure Rating 

 NEMA Type 4 for indoor applications 
 NEMA Type 12 for outdoor applications

Power Consumption

   

 SV / SV-DLE 1005/604  20VA
 SV / SV-DLE 1007/604  20VA
 SV / SV-DLE 1010/604  25VA
 SV / SV-DLE 1012/604  25VA
 SV / SV-DLE 1015/604  45VA
 SV / SV-DLE 1020/604  45VA   

 

         

ATTENTION

 • Read these instructions carefully.
 • Failure to follow them and/or improper installation may     
    cause explosion, property damage and injuries.
 • The system must meet all applicable national and local 
    code requirements such as but not limited to the follow-
    ing fuel gas codes: NFPA 54, IFGC (International Fuel Gas 
    Code), or CSA B149.1 (for Canada) or the following 
    equipment codes and standards: CSD-1, NFPA 86, 
    ANSI Z83.4/CSA 3.7, ANSI Z83.18, 
    ANSI Z21.13/ CSA 4.9, or CSA B149.3 (for Canada).

•  Installation must be done with the supervision of a 
    licensed burner technician.
•  Check the ratings in the specifications to make sure that 
    they are suitable for your application.
•  Never perform work if gas pressure or power is applied,       
    or in the presence of an open flame.
 • Once installed, perform a complete checkout including  
    leak testing.
 • Verify proper operation after servicing.