DFANA-M: network analyzer module for
Domino
bus
DFANA-M and DFANA-S modules allow the measurements
of electrical variables of a three-phase network and it is
available, under request only, in special version for sin-
gle-phase network. DFANA-M module interfaces directly to
the
Domino
bus, thus making the measurements immedi-
ately available and easy to use. The measurements are
also showed on the front panel of DFANA-S by through a
back-lighted LCD display.
Among the several available measurements, shown on the
display of DFANA-S (with the symbol showed in the follow-
ing table), DFANA-M can report on the bus up to 20 vari-
ables to be chosen among the following:
Variables
Symbol
Measured
units
3 Phase voltages (*)
V1N V2N V3N
[V]
3 Linked voltages (*)
V12 V23 V31
[V]
1 Linked average voltage (*)
Vtm
[V]
3 Currents (**)
I1 I2 I3
[A]
1 Average current (**)
Itm
[A]
3 Active powers
P1 P2 P3
[W]
1 Total active power
Ptot
[W]
3 Reactive powers
Q1 Q2 Q3
[VAR]
1 Total reactive power
Qtot
[VAR]
3 Apparent powers
S1 S2 S3
[VA]
1 Total apparent powers
Stot
[VA]
3 Phase power factors
PF1 PF2 PF3
-
1 Total power factor
PF
-
1 Frequency
Frequency
[Hz]
1 Positive active energy
Wh(+)
[Wh]
1 Negative active energy
Wh(-)
[Wh]
1 Positive reactive energy
VARh(+)
[VARh]
1 Negative reactive energy
VARh(-)
[VARh]
1 Hour-meter
Hour Meter
[ore]
1 Cabinet temperature
Temperature
[°C]
(*): Voltages are sent on the bus multiplied x 10
(**): Currents are sent on the bus multiplied x 100
DFANA_M module also provides the possibility to reset:
✗
Energies
✗
Hour-meter
DFNA-M module features a 2-way fixed terminal block for
the connection to
Domino
bus and a 3-way fixed terminal
blocks for the connection to DFANA-S module.
For information about terminal blocks, connections and the
several possible settings of the measurements section of
DFANA-S module, refer ti the related User's Manual
(DFANA-S_xxMIT).
Near to the bus terminal block, DFANA-M module features
a small pushbutton and a green LED that shows the oper-
ating status; this LED normally flashes every 2 seconds
about to signal that the module is properly connected to the
bus. DFANA-M module is housed in a standard 2M modu-
lar box for rail mounting
Note:
the setting up of DFANA-M module requires BDTools or
DCP IDE software.
Address programming
DFANA-M module takes, in dynamic mode, up to a maxi-
mum of 20 consecutive input addresses and, if enabled, 1
output address equal to the base address; the address can
be assigned by DFPRO programmer or by BDTools or
DCP IDE. A white label on the front panel allows the writing
of the assigned base address for an immediate visual iden-
tification. The effective amount of used addresses depends
on the number of measurements to be transferred on the
bus.
Module connection
The following schematic diagram shows the connection be-
tween DFANA-M. DFANA-S and and
Domino
bus.
A+
B-
9
7
6
4
3
1
|
65 64
2
5
8
11
20
21
ENTER
L1
L2
L3
N
SUPPLY
POWER
VOLTAGE INPUT
L1
L2
L3
CURRENT INPUT
A+ B-
RS485
DUEMMEGI
DFANA-S
+
BUS
_
RS485
A+ B- Sh
DUEMMEGI
MILANO-ITALY
ADDRESS
DFANA-M
+ _
Domino
P
A
T
E
N
T
E
D
For details about the connection to the AC line and to the
aux power supply, refer to the related User's Manual
(DFANA-S_xxMIT.
DUEMMEGI
s.r.l. - Via Longhena, 4 - 20139 MILANO
Tel. 02/57300377 - Fax 02/55213686 –
www.duemmegi.it
Rel.: 1.2 April 2020
Page 1 of 4