164004.C03
H3
areas subject to minor shock, vibration and temperature or atmospheric variations. In
marine applications, this is equivalent to a fixed installation inside the superstructure of
the vessel. It is recommended that, unless very rigorous thermal management is a
factor of the TP400 installation, that this is the most benign environment that should be
used for reliability estimation.
Mobile (vehicular mounted or portable and uncontrolled): Conditions more severe
than Fixed, mostly for shock and vibration. More maintenance limited and susceptible
to operator abuse. Typical applications are the mobile IT, portable operating
equipment and portable test equipment. In marine applications, this is equivalent to a
fixed installation inside the engine room of the vessel.
Note that Table H1 and Figures H1 and H2 provide separate data for each of these
usage environments.
H.2.4 Sensitivity
Analysis
The highest failure rate item in the TP400 at 25ºC is the Geode GXm processor,
accounting for 3.7% of the overall failure rate. The next highest, the 32M byte SODIMM
SDRAM, accounts for 3.2% of the failure rate.
The highest failure rate item in the TP400 at 75ºC is the switch mode PSU chip
(LT1506CR-3.3SYNC), accounting for 5.5% of the overall failure rate. The next
highest, the Geode GX1 processor, accounts for 5.1% of the failure rate.
These figures are not at all excessive, given the range of complexity of the
components used.
H.3 RELIABILITY
DATA
The reliability calculations are presented in Table H1 and Figures H1 and H2. It should
be noted that Mean Time to Failure and Unit Failure Rate per Annum have a fixed
relationship: (Unit Failure Rate per Annum = Reciprocal [Mean Time to Failure in
hours/(24 x 365)]).
The data represent the reliability performance under the assumption that usage is
continuous. If the usage is not continuous then the environment “Benign” is not
applicable; the Fixed environment is the most benign that can be achieved. Calculation
of failure rates should then be conducted by estimating the calendar reliability on the
basis of the elapsed calendar time taken to reach the applicable MTTF.
For example: a TP400 is in use within a control room environment. It runs for 6 hours
per day, 7 days per week. The operating temperature of the TP400 is found to be
70ºC:
MTTF (at 70ºC in Fixed environment): 31220 hours.
Mean calendar time to failure = 36767/6 = 6128 days = 16.79 years
Содержание 104-plus
Страница 2: ... This page is intentionally left blank ...
Страница 4: ... This page is intentionally left blank ...
Страница 76: ...66 158004 B00 This page is intentionally left blank ...
Страница 86: ...B8 158004 B00 This page is intentionally left blank ...
Страница 88: ...C2 158004 B00 FIGURE C1 MAIN BOARD TOP COMPONENT PLACEMENT ...
Страница 89: ...158004 B00 C3 FIGURE C2 MAIN BOARD BOTTOM COMPONENT PLACEMENT ...
Страница 90: ...C4 158004 B00 FIGURE C3 DAUGHTER BOARD TOP COMPONENT PLACEMENT ...
Страница 91: ...158004 B00 C5 FIGURE C4 DAUGHTER BOARD BOTTOM COMPONENT PLACEMENT ...
Страница 92: ...C6 158004 B00 FIGURE C5 MAIN BOARD MECHANICAL DIMENSIONS ...
Страница 93: ...158004 B00 C7 FIGURE C6 DAUGHTER BOARD MECHANICAL DIMENSIONS ...
Страница 94: ...C8 158004 B00 This page is intentionally left blank ...
Страница 100: ...D6 158004 B00 This page is intentionally left blank ...
Страница 116: ...E16 158004 B00 This page is intentionally left blank ...
Страница 134: ...H6 164004 C03 This page is Intentionally left blank ...
Страница 136: ...J2 164004 C03 FIGURE J1 TP400ET MECHANICAL DRAWINGS FIGURE J2 TP400ET CIRCUIT DIAGRAM ...
Страница 138: ...K2 158004 B00 FIGURE K1 TP300USB MECHANICAL DRAWINGS FIGURE K2 TP300USB CIRCUIT DIAGRAM ...