Operation
84
6.7.3
ENGINE RUNNING
Once the engine is running, the
Warm Up
timer, if selected, begins, allowing the engine to stabilise
before accepting the load.
Load will be automatically transferred from the mains supply to the generator.
NOTE:-The load transfer signal remains inactive until the Oil Pressure has risen. This
prevents excessive wear on the engine.
In test mode, the set will continue to run
on load
until either:
•
The
stop button
is pressed – The set will immediately stop
•
The
auto button
is pressed. The set will observe all auto mode start requests and
stopping timers before beginning the
Auto mode stopping sequence
.