Operation
82
6.6.3
ENGINE RUNNING
In manual mode, the load is not transferred to the generator unless a ‘loading request’ is made.
A loading request can come from a number of sources.
•
Pressing the
transfer to generator
button
•
Mains supply out of limits (DSE7420 only)
•
Activation of an auxiliary input that has been configured to
remote start on load
•
Activation of the inbuilt exercise scheduler if configured for ‘on load’ runs.
NOTE:-The load transfer signal remains inactive until the Oil Pressure has risen. This
prevents excessive wear on the engine.
Once the load has been transferred to the generator, it will not be automatically transferred back to
the mains supply. To manually transfer the load back to the mains either:
•
Press the
Transfer to Mains
button (DSE7420 only)
•
Press the
Open Generator
button (DSE7410 only)
•
Press the
Auto Mode
button to return to automatic mode.
For further details of breaker control, see the section entitled “controls and indications” elsewhere in
this manual.
6.6.4
MANUAL FUEL PUMP CONTROL
•
Navigate to the instruments page using the
buttons and locate FUEL LEVEL.
is
shown on the module display to indicate that this feature is available.
•
Press and hold the
button to energise the transfer pump. The pump starts two seconds
after the button is pressed.
•
Release the
button to de-energise the transfer pump.
6.6.5
MANUAL SPEED CONTROL
•
Navigate to the instruments page using the
buttons and locate ENGINE SPEED.
is
shown on the module display to indicate that this feature is available.
•
Press the
button to enter edit mode
•
Press
(up or down) to change the engine speed.
•
Press the
button again to exit the editor and leave the engine running at the newly
selected speed.