Specification
9
3.4 TERMINAL SPECIFICATION
NOTE: For purchasing additional connector plugs from DSE, please see the section
entitled Maintenance, Spares, Repair and Servicing elsewhere in this document.
Connection Type
Two part connector.
•
Male part fitted to
module
•
Female part supplied in
module packing case -
Screw terminal, rising
clamp, no internal
spring.
Example showing cable entry and screw
terminals of a 10 way connector
Minimum Cable Size
0.5mm² (AWG 24)
Maximum Cable Size
2.5mm² (AWG 10)
3.5 POWER SUPPLY REQUIREMENTS
Minimum Supply Voltage
8V continuous
Cranking Dropouts
Able to survive 0V for 100ms providing the supply was at least
10V before the dropout and recovers to 5V afterwards.
Maximum Supply Voltage
35V continuous (60V protection)
Reverse Polarity Protection
-35V continuous
Maximum Operating Current
96mA at12V
85mA at 24V
Maximum Standby Current
51mA at 12V
47mA at 24V
Maximum Current When In
Sleep Mode
35mA at 12V
32mA at 24V
Maximum Current When In
Deep Sleep Mode
Less than
10µA at 12V
Less than
10µA at 24V
3.5.1 MODULE SUPPLY INSTRUMENTATION DISPLAY
Range
0V-70V DC (note Maximum continuous operating voltage of 35V DC)
Resolution
0.1V
Accuracy
1% full scale (±0.7V)