Specification
8
3 SPECIFICATIONS
3.1 SHORT NAMES
Short Name
Description
DSE4000,DSE4xxx
All modules in the DSE4000 range.
DSE4600,DSE46xx
All modules in the DSE4600 range.
DSE4610
DSE4610 module/controller
DSE4620
DSE4620 module/controller
3.2 OPERATING TEMPERATURE
Module
Description
DSE46xx
-30ºC to +70ºC (-40ºC to +70ºC for variants fitted with display heaters)
3.3 REQUIREMENTS FOR UL CERTIFICATION
Screw Terminal
Tightening
Torque
•
4.5 lb-in (0.5 Nm)
Conductors
•
Terminals suitable for connection of conductor size 12 AWG – 26 AWG
(0.5mm² to 2.0mm²).
•
Conductor protection must be provided in accordance with NFPA 70, Article
240
•
Low voltage circuits (35 volts or less) must be supplied from the engine
starting battery or an isolated secondary circuit.
•
The communication, sensor, and/or battery derived circuit conductors shall be
separated and secured to maintain at least ¼” (6mm) separation from the
generator and mains connected circuit conductors unless all conductors are
rated 600 Volts or greater.
Current Inputs
•
Must be connected through UL Listed or Recognized isolating current
transformers with the secondary rating of 5A max.
Communication
Circuits
•
Must be connected to communication circuits of UL Listed equipment
Output Pilot Duty
•
0.5 A
Mounting
•
Suitable for use in type 1 Enclosure Type rating with surrounding air
temperature -22ºF to +158ºF (-30ºC to +70ºC)
•
Suitable for pollution degree 3 environments when voltage sensing inputs do
not exceed 300V. When used to monitor voltages over 300V device to be
install in an unventilated or filtered ventilation enclosure to maintain a pollution
degree 2 environment.
Operating
Temperature
•
-22ºF to +158ºF (-30ºC to +70ºC)
Storage
Temperature
•
-40ºF to +176ºF (-40ºC to +80ºC)