Front Panel Configuration
32
Parameters with multiple choices use the following identification tables for the parameter values:
INPUT SOURCE LIST
0
Not used
1
Alarm Reset
2
Alarm Mute
3
Auto Restore Inhibit
4
Auto Start Inhibit
5
Auxiliary S2 Available
6
Auxiliary S1 Fail
7
S2 Load Inhibit
8
S2 Closed Auxiliary
9
Inhibit Scheduled Run
10
Lamp Test
11
Load Shedding
12
S1 Closed Auxiliary
13
S1 Load Inhibit
14
Open / Close S2
15
Open / Close S1
16
Panel Lock
17
Remote Start off-load
18
Remote Start on-load
19
Simulated S1 available
20
Simulated S2 available
INPUT POLARITY LIST
INPUT ARMING LIST
Index
Action
Index
Arming
0
Close to Activate
0
Always
1
Open to Activate
1
From Safety On
2
From Starting
OUTPUT POLARITY LIST
3
Never
Index
Arming
0
Energise
INPUT ACTION LIST
1
De-energise
Index
Action
0
Electrical Trip
AC SYSTEM
1
Shutdown
Index
Type
2
Warning
0
3 phase 4 wire
1
Single phase 2 wire
2
3 phase 3 wire
3
2 phase 3 wire (L1-L2)
4
2 phase 3 wire (L1-L3)
5
3 phase 4 wire (Delta)