Installation
13
4 INSTALLATION
4.1 TERMINAL DESCRIPTION
4.1.1 DC SUPPLY & DC OUTPUTS.
PIN No
DESCRIPTION
CABLE SIZE
NOTES
1
DC Plant Supply Input
(Negative)
2.5mm²
AWG 13
2
DC Plant Supply Input
(Positive)
2.5 mm²
AWG 13
(Recommended Maximum Fuse 15A anti-surge)
Supplies the module (2A anti-surge requirement) and all output
relays
3
Output A
1.0mm²
AWG 18
Volts free relay (8A rated)
4
Output A
1.0mm²
AWG 18
Volts free relay (8A rated)
5
Output B
1.0mm²
AWG 18
Volts free relay (8A rated)
6
Output B
1.0mm²
AWG 18
Volts free relay (8A rated)
7
Output E
1.0mm²
AWG 18
Plant Supply Positive from terminal 7. 2 Amp rated.
8
Output F
1.0mm²
AWG 18
Plant Supply Positive from terminal 8. 2 Amp rated.
9
Output G
1.0mm²
AWG 18
Plant Supply Positive from terminal 9. 2 Amp rated.
10
Output H
1.0mm²
AWG 18
Plant Supply Positive from terminal 10 2 Amp rated.
4.1.2 DIGITAL INPUTS.
4.1.3 VOLT FREE OUTPUTS.
PIN No
DESCRIPTION
CABLE SIZE
NOTES
23
Output C
1.0mm²
AWG 18
User configured volt free output (N/O)
24
Output C
1.0mm²
AWG 18
User configured volt free output (Common)
25
Output C
1.0mm²
AWG 18
User configured volt free output (N/C)
26
Output D
1.0mm²
AWG 18
User configured volt free output (N/O)
27
Output D
1.0mm²
AWG 18
User configured volt free output (Common)
28
Output D
1.0mm²
AWG 18
User configured volt free output (N/C)
PIN
No
DESCRIPTION
CABLE SIZE
NOTES
11
Input A
1.0mm²
AWG 18
Configurable input. Connects to plant supply negative
12
Input B
1.0mm²
AWG 18
Configurable input. Connects to plant supply negative
13
Input C
1.0mm²
AWG 18
Configurable input. Connects to plant supply negative
14
Input D
1.0mm²
AWG 18
Configurable input. Connects to plant supply negative