Description of Controls 

 

18 

5.2  GRAPHICAL DISPLAY 

 

4- line, 64 x 132 small Graphic Display with LED Backlight 

Icon and numeric display. Switch to select ‘Icon’ or ‘English’ display 

Software controlled contrast  

Mimic of Text insert / 4x indicators via LCD 

 

5.2.1  DISPLAY PAGES 

 

It is possible to scroll to display the different pages of information by repeatedly operating the scroll button 

  

 

Once selected the page will remain on the LCD display until the user selects a different page or after an extended 
period of inactivity, the module will revert to the status display. 
 
When scrolling manually, the display will automatically return to the Status page if no buttons are pressed for the 
duration of the configurable LCD Page Timer

 

If an alarm becomes active while viewing the status page, the display shows the Alarms page to draw the 
operator’s attention to the alarm condition. 
 
At power up, the display will show the software version, and then display the default display screen, which will 
display Mains instrumentation.  
 

5.2.1.1  STATUS 

 
Displays voltage operational status information 
 
Example : 
 

 

 
 

5.2.1.2  INSTRUMENTATION 

 
The instrumentation page contains the following information 
 
S1 Voltage L-N 
S1 Voltage L-L 
S1 Frequency 
S2 Voltage L-N 
S2 Voltage L-L 
S2 Frequency 
Battery Voltage 
Scheduler 
 
Example:: 

Содержание DSE331

Страница 1: ...DSE331 Operator Manual ISSUE 3 DEEP SEA ELECTRONICS PLC DSE331 ATS Controller Operators Manual Document Number 057 146 Author Allan Jones...

Страница 2: ...s publication is owned by their respective companies Deep Sea Electronics Plc reserves the right to change the contents of this document without prior notice Amendments List Issue Comments Minimum Mod...

Страница 3: ...N SEALING GASKET 9 3 8 APPLICABLE STANDARDS 10 3 9 ENCLOSURE CLASSIFICATIONS 11 3 9 1 IP CLASSIFICATIONS 11 3 9 2 NEMA CLASSIFICATIONS 12 4 INSTALLATION 13 4 1 TERMINAL DESCRIPTION 13 4 1 1 DC SUPPLY...

Страница 4: ...OAD SHED INPUT 25 6 4 5 1 4 TIMING DIAGRAM 25 6 4 5 2 CHECK SYNCHRONISING IS ENABLED 26 6 4 5 2 1 TRANSFER TO S2 26 6 4 5 2 2 TRANSFER TO S1 26 6 4 5 2 3 LOAD SHED INPUT 26 6 4 5 2 4 TIMING DIAGRAM 26...

Страница 5: ...ol the transfer of the load from one supply to another typically the mains supply and a standby generator or two mains supplies The user also has the facility to view the system operating parameters v...

Страница 6: ...ATIONS 3 1 PART NUMBERING 0331 001 01 At the time of this document production there have been no revisions to the module hardware Product type Variant Hardware revision Revision 1 001 DSE 331 Auto Tra...

Страница 7: ...RMINAL SPECIFICATION Connection type Screw terminal rising clamp no internal spring Min cable size 0 5mm AWG 24 Max cable size 2 5mm AWG 10 3 3 S1 S2 VOLTAGE FREQUENCY SENSING Measurement type True RM...

Страница 8: ...A Open circuit voltage 12V 1V 3 5 OUTPUTS 3 5 1 CONFIGURABLE NORMALLY OPEN RELAY OUTPUTS A B Number 2 Configurable outputs A B Type Volts free normally open contacts Rating 8A 35VDC 3 5 2 CONFIGURABLE...

Страница 9: ...clip are inside their allotted slots Turn the fixing clip screws clockwise until they make contact with the panel fascia Turn the screws a little more to secure the module into the panel fascia Care s...

Страница 10: ...08 NEMA rating Approximate 12 Front of module when installed into the control panel with the optional sealing gasket 2 Front of module when installed into the control panel WITHOUT being sealed to the...

Страница 11: ...t enclosure is tilted at an angle up to 15 from its normal position drops falling at an angle 3 Protected against ingress of solid objects with a diameter of more than 2 5 mm Tools wires etc with a th...

Страница 12: ...Provides a degree of protection against limited amounts of falling water and dirt 3 IP64 Provides a degree of protection against windblown dust rain and sleet undamaged by the formation of ice on the...

Страница 13: ...ive from terminal 9 2 Amp rated 10 Output H 1 0mm AWG 18 Plant Supply Positive from terminal 10 2 Amp rated 4 1 2 DIGITAL INPUTS 4 1 3 VOLT FREE OUTPUTS PIN No DESCRIPTION CABLE SIZE NOTES 23 Output C...

Страница 14: ...end 2A fuse 18 S2 Neutral N input 1 0mm AWG 18 Connect to S2 Neutral terminal AC 4 1 6 PC CONFIGURATION INTERFACE CONNECTOR DESCRIPTION CABLE SIZE NOTES Socket for connection to PC with DSE Configurat...

Страница 15: ...Genset manufacturers and panel builders may use these diagrams as a starting point however you are referred to the completed system diagram provided by your system manufacturer for complete wiring de...

Страница 16: ...TION OF CONTROLS The following section details the function and meaning of the various controls on the module Display Scroll button Common Alarm Indicator S1 breaker control Main status display Select...

Страница 17: ...provides a quick start guide to the module s operation 5 1 1 MODE SELECTION OPERATION NOTE For further details see the section entitled MODE SELECTION elsewhere in this manual Press button until pref...

Страница 18: ...the status display When scrolling manually the display will automatically return to the Status page if no buttons are pressed for the duration of the configurable LCD Page Timer If an alarm becomes ac...

Страница 19: ...ail alarm The Switching device has failed to operate Failed to start The engine has not fired after the preset number of start attempts Failed to stop The module has detected a condition that indicate...

Страница 20: ...e S2 load switch This button selects the preferred mode of operation to complete the selection press the button Automatic mode This mode allows the module to control the function of the load switching...

Страница 21: ...request is still present at the end of the start delay timer the Start and Run S2 output will be energised After the generator has started it will enter the warming up timer If S2 fails to become ava...

Страница 22: ...is given for Transfer to S1 The fascia mounted transfer buttons are pressed when configured The module mode is changed to AUTO mode The system may then transfer back to mains supply automatically if...

Страница 23: ...There is no start delay in this mode of operation The start request is sent to the generator via a digital output configured to Start and Run S2 If S2 fails to become available before S2 fail delay t...

Страница 24: ...n the input is deactivated the breaker is closed again if appropriate 6 4 3 LOAD SHEDDING If an input configured to Load Shed is activated outputs set to Open S1 and Open S2 will energise and inputs c...

Страница 25: ...s whichever occurs first When the S2 Closed Auxiliary indicates S2 breaker has opened the transfer timer begins When the transfer timer expires the module attempts to close S1 breaker by energising th...

Страница 26: ...er from S2 to S1 it activates the check sync function When S1 and S1 are within the phase and frequency window the module energises the Open S2 and Close S1 outputs simultaneously These outputs are de...

Страница 27: ...AUTO mode the generator is called to start if not already running and will be placed on load when available If the S1 supply fails while the S2 is running in MANUAL mode the 331 ATS module transfers l...

Страница 28: ...e allows the operator limited customising of the way the module operates Use the module s navigation buttons to traverse the menu and make value changes to the parameters Increase value next item Edit...

Страница 29: ...Press and hold the button to exit the editor the configuration icon will be removed from the display 8 2 ADJUSTABLE PARAMETERS CONFIGURATION EDITOR When viewing the configuration editor Press to selec...

Страница 30: ...Output Source Polarity 411 Digital Output F Source 0 Output Source List 412 Digital Output F Polarity 0 Output Source Polarity 413 Digital Output G Source 0 Output Source List 414 Digital Output GPol...

Страница 31: ...n On 1 Off 0 716 Over voltage return Mains Option 0 V 717 Over voltage trip Mains Option 0 V 718 Under frequency enable Mains Option On 1 Off 0 719 Under frequency Mains Option 0 0 Hz 720 Under freque...

Страница 32: ...S1 Load Inhibit 14 Open Close S2 15 Open Close S1 16 Panel Lock 17 Remote Start off load 18 Remote Start on load 19 Simulated S1 available 20 Simulated S2 available INPUT POLARITY LIST INPUT ARMING LI...

Страница 33: ...Fail to start 18 Fail to stop 19 Fail to reach loading voltage 20 Fail to reach loading frequency 21 S2 Available 22 S2 Failure Latched 23 S2 Failure Unlatched 24 S2 In Limits 25 S2 Load Inhibited 26...

Страница 34: ...itional plugs from DSE please contact our Sales department using the part numbers below Module terminal designation Plug description Part No 1 10 10 way 5 08mm 007 450 11 14 4 way 5 08mm 007 444 15 22...

Страница 35: ...SUBSTANCES Directive 2002 95 EC 2006 To remove specified hazardous substances Lead Mercury Hexavalent Chromium Cadmium PBB PBDE s Exemption Note Category 9 Monitoring Control Instruments as defined in...

Страница 36: ...update of the controller 12 1 2 PC TO CONTROLLER DIRECT CONNECTION To connect a 331 ATS module to a PC the following items are required DSE331 series module Configuration Suite software Supplied on c...

Страница 37: ...This Page is Intentionally blank 37...

Страница 38: ...This Page is Intentionally blank 38...

Отзывы: