10

Programming Descriptions

[02]

Mode 2 - (2) 24-Hour Zones

In this mode, the YEL and GRN
terminals on the Skyroute
CL3050 will be used as zone
inputs.  These zones will support
the DSC standard EOL configura-
tion and loop response.  Pro-
gramming sections will allow the
installer to change the default
zone types and attributes. The
Skyroute CL3050 will continu-
ously monitor these zones and
transmit any alarms that occur to
the central station.

NOTE: 

Use Mode 2 for UL residential burglary installations.

[03]

Mode 3 - (8) 24-Hour Zones

In this mode, the Skyroute
CL3050 is connected to a
PC5108 zone expander using the
corresponding RED, BLK, YEL and
GRN terminals.  The Skyroute
CL3050 will drive the Keybus to
communicate with the PC5108.
A +12V

DC

 supply connected to

the RED and BLK terminals is
required when using this mode.
The Programming sections allow the installer to change the default zone types
and attributes. The Skyroute CL3050 continuously monitors these zones and
transmits any alarms that occur to the central station.

NOTES:  

This configuration can not be used with an AC supply.

Jumpers on the PC5108 must be set as follows:

J1
J2
J3

ON
OFF
ON

J4
J5
J6

OFF
OFF
ON

Default - 

[01 -03]  dependant on start up configuration.

NOTES:  

Use Mode 3 for UL Installations.

PC5108 must be installed in its own enclosure or in the same cabinet as the con-
trol panel.
All connections are power limited.

[11] Skyroute CL3050 Configuration Options 1

Option 1 - A Channel Selected/ B Channel Selected. 

All Modes

This Option determines whether cellular channel 

“B” 

or channel 

“A”

 is used

. In

Canada, Channel B is used (Default). In the USA refer to the SID list for the chan-
nel of the cellular service provider in your area. 

Default -

 Channel B

Option 2 - Normally Closed Loops/ End-of-line Resistors                

Mode 2, 3

Normally Closed Loops can be wired as shown. Multiple Normally Closed con-
tacts can be wired in series. For Double or Single EOL resistors this option must be
set to 

OFF

Default -

 Normally Closed (N/C) Loops.

NOTE: 

Option must be OFF for UL Installations.

Input Voltage
10.6-14 V

or V

AC

DC

Zone 1 Input

Zone 2 Input

Zone Common

Trouble Output

RED    BLK

YEL    GRN   COM   PGM

RED    BLK

YEL    GRN   COM   PGM

+12 V

DC

Ground

To Keybus
Connections
on PC5108

System Common

Trouble Output

Содержание Skyroute CL3050 ver 1.2

Страница 1: ...rSeries keypads Installation Programming Guide WARNING This manual contains information on limitations regarding product use and function and information on the limitations as to liability of the manu...

Страница 2: ...found on the authorized Installer Card sent with the Dealer Confirmation Form Installer PIN Number 4 digits I___I___I___I___I Each Installer provided a 4 digit PIN number on the Dealer Enrollment Form...

Страница 3: ...02 Zone 3 8 Definitions 9 03 Zone 1 2 Loop Response 9 10 Skyroute CL3050 Mode of Operation 9 11 Skyroute CL3050 Configuration Options 1 10 12 Skyroute CL3050 Configuration Options 2 11 13 Skyroute CL3...

Страница 4: ...ii NOTE...

Страница 5: ...rglar alarm reporting code to Connect 24 Refer to the appropriate control panel Installation Manual NOTE Not for UL Listed installations Mode 2 2 Zone Panel In Mode 2 the system will configure itself...

Страница 6: ...y all PowerSeries Keypads PC5508 KP5508Z 8 Zone LED keypad PC5516Z KP5516Z 16 Zone LED keypad PC5532Z KP5532Z 32 Zone LED keypad LCD5500Z KPL5500Z Programmable Message LCD Keypad LCD5501Z KP5501Z Fixe...

Страница 7: ...RF noise or interference Refer to section 6 Programming Descriptions section 10 for zone wir ing details NOTE Generally the higher the location and the closer that the Skyroute CL3050 is to an outsid...

Страница 8: ...tton for 2 seconds will send a test transmission to the central station via Connect 24 Refer to Enroll Button in Section 3 Controls and indicators for test transmission details Mode 1 Disable the tele...

Страница 9: ...of flashes as indicated below No of Flashes Indication 1 2 3 4 5 6 7 8 9 No trouble conditions present Low battery Input supply failure Not enrolled at Connect 24 No service available Radio failure PC...

Страница 10: ...iled RSSI status indicated above Holding this button down for a period of 2 seconds continuously will cause the Skyroute CL3050 to send a test transmission to Connect 24 this long debounce will be ind...

Страница 11: ...d it will look for a PC5108 zone expander module If a zone expander is found it will automatically configure itself for mode 3 If no Keybus modules are present the Skyroute CL3050 will power up in mod...

Страница 12: ...odes 2 3 When the Skyroute CL3050 is in Mode 2 or 3 there are 14 options that can be programmed as zone types All of the zone types with the exception of 00 null zone 13 CL3050 communications zone and...

Страница 13: ...t for any steady bell the Skyroute CL3050 will send a generic Burglary event The GRN terminal is a trouble input which can be connected to a system output to alert the Skyroute CL3050 of a system TLM...

Страница 14: ...tation NOTES This configuration can not be used with an AC supply Jumpers on the PC5108 must be set as follows J1 J2 J3 ON OFF ON J4 J5 J6 OFF OFF ON Default 01 03 dependant on start up configuration...

Страница 15: ...edure with Connect 24 IF the Skyroute CL3050 is reset to the default settings this option must be set to ON for the Skyroute CL3050 to resume communications Default Not Enrolled Options 7 8 System Use...

Страница 16: ...ith the cellular radio Default ON Option 6 PC5108 Failure Mode 3 This trouble is indicated if a PC5108 supervisory or Keybus fault occurs NOTE The PC5108 tamper is communicated only therefore it can o...

Страница 17: ...0 will randomly generate this value Because one test transmission weekly is the most common configuration this will allow the installer to setup the Skyroute CL3050 without keypad programming Option 1...

Страница 18: ...ignored until that group s timer has expired See table below for zone type grouping Zone Type Detailed Reporting Code Generic Reporting Code Null Burglary Fire Panic Technical Gas Heat Medical Emerge...

Страница 19: ...050 communications zone is violated Default OFF 22 Input Supply Fail TX Delay All Modes This value determines the delay default 0700 7 hrs before an input supply fail ure reporting code is sent if pro...

Страница 20: ...Hex 0 1 second increments mode 2 only Default Default 05 I___I___I Zone 1 05 I___I___I Zone 2 10 Skyroute CL3050 Mode of Operation Default Default 01 I___I___I 01 Bell Follower 02 2 Zone 03 8 zone PC...

Страница 21: ...N I___I 4 No Service Available Disabled ON I___I 5 Radio Failure Disabled ON I___I 6 PC5108 Failure Disabled ON I___I 7 Failure to Communicate Disabled OFF I___I 8 Skyroute CL3050 Tamper Disabled 15 S...

Страница 22: ...tores Disabled OFF I___I 5 Zone Tamper Disabled OFF I___I 6 Zone Tamper Restores Disabled ON I___I 7 System Maintenance Events Disabled ON I___I 8 Generic Zone Reporting Detailed Zone Reporting 21 Sys...

Страница 23: ...19 Programming Worksheets 24 Number of Attempts Default Range 03 I___I___I 01 FF Hex 25 Response Wait Time Default Range FA I___I___I 01 FF Hex seconds For UL Installations program 5A...

Страница 24: ...Indication This value is transmitted to Connect 24 during the periodic test transmission and can be viewed after power up by pressing the enroll button SID System Identification Number ID Number of th...

Страница 25: ...ne ZHXX R140 Sprinkler Zone SAXX E110 Sprinkler Zone SHXX R110 Hold up Zone HAXX E122 Hold up Zone HHXX R122 Trouble Zone YX00 E300 Trouble Zone YZ00 R300 Zone Fault Alarms Zone Fault Restores Burglar...

Страница 26: ...TXX E373 Sprinkler Zone SJXX R373 Hold up Zone HTXX E380 Hold up Zone HJXX R380 Trouble Zone UTXX E380 Trouble Zone UJXX R380 Generic Zone Events System Events Generic Burglary BA98 E130 98 Input Supp...

Страница 27: ...EMENT This Class B digital apparatus meets all requirements of the Canadian interference causing equipment regulations Cet appareil num rique de la Classe B respecte toutes les exigences de r glement...

Страница 28: ...ital Security Controls Ltd Toronto Canada www dsc com Tech Support 1 800 387 3630 Canada US or 905 760 3036 Printed in Canada 29034673 Rev 001 Direct all comments concerning this publication to pubs d...

Отзывы: