15
4.3 Enable Supervision of Wireless Zones
NOTE (for PC5010 v1.x control panels only): For UL Listed installation, Double
EOL resistors must be enabled in the PC5010 for the wireless zones to be
supervised. If normally Closed or Single EOL resistors are selected the PC5010
will not be able to supervise the wireless devices. If a wireless device stops
sending a supervisory signal (the unit stops functioning) the panel will not indi-
cate a supervisory trouble condition unless Double EOL resistors are used. In
addition, all hardwire zones must be wired for Double EOL resistors. For more
information, refer to your PC5010 v1.x Installation Manual.
NOTE (PC5010 v2.0 and higher, PC1555, PC580 only): For wireless supervi-
sion to work, you must enable the wireless zone attribute on all wireless zones
(sections [101] to [132], option [8] ON).
NOTE: The supervisory option for any panic pendants enrolled on the system
must be OFF. For UL Listed systems, the wireless zones must be programmed
as supervised.
Wireless Supervisory Window
Each wireless zone (WLS904, WLS905, WLS906 or WLS907) will send a
supervisory signal every 12 minutes. If the receiver does not receive a signal
within the time programmed for the
Wireless Supervisory Window
, it will
generate a supervisory fault.
To program the wireless supervisory window:
1. Enter [
✱
][8][Installer Code] to enter Installer Programming.
2. Enter [804] to enter the PC5132-RS Module Programming.
3. Enter sections [81].
4. Enter the time period for the supervisory window (valid entries are 01-24
hours).
5. To exit press [#].
WLS908 Panic Pendant
The panic pendant does not transmit a supervisory signal. This is so that the
user will be able to take it away from the premise. You must disable wireless
supervision for each zone a panic pendant is assigned to.
Disable/Enable Zone Supervision
All wireless zones have supervision enabled by default. To disable supervision
for any zone, enter the following at any system keypad:
1. Enter [
✱
][8][Installer Code] to enter Installer Programming.
2. Enter [804] to enter the PC5132-RS Module Programming.
3. Enter sections [82], [83], [84] and [85]. Disable or enable supervision for
each wireless zone by turning each relevant option on or off.
4. To exit press [#].