background image

34

product identifier that has the format. US: AAAEQ##TXXXX. The digits represented by ## are the REN without a decimal point (e.g., 03 is a REN of

0.3). For earlier products, the REN is separately shown on the label.

Incidence of Harm

If this equipment LE4020/LE4020CF causes harm to the telephone network, the telephone company will notify you in advance that temporary

discontinuance of service may be required. But if advance notice is not practical, the Telephone Company will notify the customer as soon as possible.

Also, you will be advised of your right to file a complaint with the FCC if you believe it is necessary.

Changes in Telephone Company Equipment or Facilities

The Telephone Company may make changes in its facilities, equipment, operations or procedures that could affect the operation of the equipment. If this

happens the Telephone Company will provide advance notice in order for you to make necessary modifications to maintain uninterrupted service.

Equipment Maintenance Facility

If trouble is experienced with this equipment for repair or warranty information, please contact the facility indicated below. If the equipment is causing

harm to the telephone network, the Telephone Company may request that you disconnect the equipment until the problem is solved. This equipment is of

a type that is not intended to be repaired by the end user.

DSC c/o APL Logistics, 2600 West Pointe Dr.., Lithia Springs, GA 30122

Additional Information

Connection to party line service is subject to state tariffs. Contact the state public utility commission, public service commission or corporation

commission for information. Alarm dialling equipment must be able to seize the telephone line and place a call in an emergency situation. It must be able

to do this even if other equipment (telephone, answering system, computer modem, etc.) already has the telephone line in use. To do so, alarm dialling

equipment must be connected to a properly installed RJ-31X jack that is electrically in series with and ahead of all other equipment attached to the same

telephone line. Proper installation is depicted in the figure below. If you have any questions concerning these instructions, you should consult your

telephone company or a qualified installer about installing the RJ-31X jack and alarm dialling equipment for you.

ISED Compliance Statement

This Equipment meets the applicable Industrial, Scientific and Economic Development (ISED) Terminal Equipment Technical Specifications. This is

confirmed by the registration number. The abbreviation, IC, before the registration number signifies that registration was performed based on a Declaration

of Conformity indicating that ISED Canada technical specifications were met. It does not imply that that ISED Canada approved the equipment. The

Ringer Equivalence Number (REN) for this terminal equipment is 0.0. The REN assigned to each terminal equipment provides an indication of the

maximum number of terminals allowed to be connected to a telephone interface. The termination on an interface may consist of any combination of devices

subject only to the requirement that the sum of the Ringer Equivalence Numbers of all devices does not exceed 5.

IC:160A-LE4020

Cet équipement est conforme aux spécifications techniques applicables aux équipements terminaux d'ISED Canada. Ceci est confirmé par le numéro

d'enregistrement. L'abréviation IC précédant le numéro d'enregistrement signifie que l'enregistrement a été effectué sur la base de la Déclaration de

conformité indiquant que le produit est conforme aux spécifications techniques d'ISED Canada. Ceci n'implique pas que le produit ait été approuvé par

Industrie Canada.

Le nombre équivalent de sonneries (REN) de cet appareil terminal est 0.0. Le REN attribué à chaque équipement terminal fournit une indication sur le

nombre maximum de terminaux pouvant être connectés sur une interface téléphonique. La terminaison sur une interface peut constituer en n'importe quelle

combinaison d'appareils, à la condition seulement que la somme des Nombres équivalents de sonneries de tous les appareils ne soit pas supérieure à 5.

This Class B digital apparatus meets all requirements of the Canadian interference-causing equipment regulations. Cet appareil numérique de la Classe B

respecte toutes les exigences de règlement sur le matériel brouilleur du Canada.

CAN ICES-3 (B) / NMB-3 (B)

The term “IC:” before the radio certification number only signifies that ISED Canada technical specifications were met.

NIST Validation of encryption algorithm AES128 certificate No. C187.

NOTICE TO USERS, INSTALLERS, AUTHORITIES HAVING JURISDICTION AND OTHER
INVOLVED PARTIES

This product incorporates field-programmable software. In order for the product to comply with the requirements in the Standard for Control Units and

Accessories for Fire Alarm Systems, UL 864, certain programming features or options must be limited to the specific values or not used at all as indicated

below.

Program Feature or Option Permitted in UL 864 (Y/N?) Possible Settings

Settings Permitted in UL 864

Supervision

Yes

5 minutes /60 minutes 5 minutes (see note below)

Inputs/Outputs

Yes

Fire/Burg signals

Fire related signals only

SMS Remote Control

No

Enable/Disable

Disable

LE4020/LE4020CF Installation Manual

Содержание LE4020

Страница 1: ...Communicator INSTALLATION MANUAL Warning This manual contains information on limitations regarding product use and function and information on the limitations as to liability of the manufacturer The...

Страница 2: ...inciples 15 5 1 Simulated Landline Mode 15 5 2 Panel Transmission Monitoring PTM 15 5 3 Cellular Communications Sequence 15 5 4 Inputs 16 5 5 Outputs 16 5 5 1 Activating the Outputs 16 5 6 Reporting C...

Страница 3: ...ling with regard to this lead acid battery Doing so will help protect the environment Some of the materials that are found within the battery could become toxic if not disposed of properly and may aff...

Страница 4: ...rmation that they have been received 1 1 Features l Dual band UMTS HSPA Penta Band LTE LE4020 LE4020CF l Advanced Carrier Selection l Bi color Wireless Signal Strength Indicator l LTE or 3G Internet c...

Страница 5: ...adapter Use internal PS4085 power supply module Without Battery 10 Vdc to 28 Vdc external power supply N A Battery Type sealed rechargeable type rated 12 V 7 Ah for 24 hr standby time plus 5 min alar...

Страница 6: ...and Rx LTE B2 1850 1910 MHz 1930 1990 MHz LTE B4 1710 1755 MHz 2110 2155 MHz LTE B5 824 849 MHz 869 894 MHz LTE B12 698 716 MHz 728 746 MHz LTE B13 777 787 MHz 746 756 MHz UMTS B2 1850 1910 MHz 1930 1...

Страница 7: ...3 4 5 6 1 4 3 7 8 9 10 11 12 Part Part 1 3G LTE antenna 7 Battery connector 2 Metal enclosure 8 Tamper switch 3 Status LEDs 9 Terminal blocks 4 Anchor screw holes 10 12 V 7Ah battery not included 5 S...

Страница 8: ...ich are not power limited Do not route any wiring over circuit boards Maintain at least 1 25 4mm separation A minimum 1 4 6 4mm of separation must be maintained at all points between Power Limited wir...

Страница 9: ...rews 2 Apply power DC and or battery The LE4020 LE4020CF is now in Placement Test mode Step 2 Determine Best Signal Location 1 Remove the screws and the front cover of the LE4020 LE4020CF metal enclos...

Страница 10: ...a carrier with a signal strength above 7 CSQ minimum of bottom signal strength LED on solid Red Blue Blue Green Top Blue Green Bottom FLASH ON OFF OFF OFF OFF FLASH ON OFF OFF OFF OFF FLASH ON OFF OFF...

Страница 11: ...ff Once the initialization sequence is complete the LE4020 LE4020CF switches to steady state operation Step 6 Mount the LE4020 LE4020CF 1 Power down the LE4020 LE4020CF by removing the DC power source...

Страница 12: ...e maximum current sink of each output must not exceed 50mA AUX 11 Auxiliary Output 9 to 14VDC Special Application Output 200 mA max for LE4020 and 100 mA max for LE4020CF Note Electrical current drawn...

Страница 13: ...so flashes once when the LE4020 LE4020CF transmits a signal and twice when it receives a kiss off from the central station Note If the LE4020 LE4020CF is programmed to be the primary communicator the...

Страница 14: ...1 OFF Wireless network trouble unable to connect to cellular network 2 OFF Battery trouble battery with low voltage output 3 OFF Input power trouble 1 Flashing Insufficient signal strength poor locat...

Страница 15: ...is in addition to the regular line voltage detection The LE4020 LE4020CF monitors the phone line for four consecutive failed attempts within a 12 minute win dow A failed attempt is assumed to have oc...

Страница 16: ...last format the control panel used to transmit an event 5 4 Inputs The LE4020 LE4020CF has four inputs that can be used to trigger specific communications These events trans mit using the Contact ID...

Страница 17: ...Restore Zone 2 Activation E12A 992 PA 992 YES Panic Alarm Zone 2 Restoral R12A 992 PH 992 YES Panic Alarm Restore Zone 3 Activation E13A 993 BA 993 YES Burglary Zone 3 Restoral R13A 993 BH 993 YES Bu...

Страница 18: ...with Swinger Shut down which limits certain trouble events to a maximum of four reports every 24 hours The condition restores and the counter resets at midnight Swinger Shutdown applies to the follow...

Страница 19: ...following troubles is present If the trouble occurs after the unit has processed the firmware update request the firmware update is not interrupted Input Power Trouble Low Battery Trouble 5 10 Low Po...

Страница 20: ...the PGM timer to a value between 1 and 255 seconds causes it to be timed The PGM activates for the programmed duration 2 Via C24 Communications program the phone number and access code used for SMS co...

Страница 21: ...ommands for the selected language 5 12 Phone Number Call Direction The PTM phone numbers to receiver group 1 or 2 are programmable The number programmed in the com municator must also be programmed as...

Страница 22: ...be programmed to communicate Contact ID or SIA over the telephone line Blue Green LED Status What it means CSQ Values Signal Strength Status Both Signal Strength LEDs ON Excellent Sig nal Strength 14...

Страница 23: ...charged to at least 12 5VDC If not wait at least 1 hour for the battery to charge l Remove the battery and measure the voltage the voltage should be at least 12VDC l Verify the input DC supply is rate...

Страница 24: ...nected l Verify correct phone line wiring l Ensure the Ringer Equivalency Number REN is not being exceeded on the line General Information Removing Connecting the antenna l To remove the antenna from...

Страница 25: ...ation must be maintained at all points between Power Limited wiring and all other Non Power Limited wiring Route wires as indicated in the diagram For UL Installations the system shall be installed in...

Страница 26: ...required for Fire Alarm Monitoring Refer to Fig 1 3 for wiring details Suggested compatible DACT models for use with LE4020CF are DSC models PC4020 with PC4701 Interface or PC5020CF with PC5700 Inter...

Страница 27: ...NNECT AC POWER TELEPHONE LINES PRIOR TO SERVICING These outputs shall be connected to zone inputs of an alarm control panel in order to provide the required trouble supervision visual and audible indi...

Страница 28: ...e mains plug and associated mains socket outlet is never obstructed The following wiring diagrams are examples of ULC Listed Fire Monitoring Installation connections Figure 1 6 Wiring Diagram for Fire...

Страница 29: ...separately listed power supply rated for the application 10 28V 700mA l All wiring connections must be run in a metallic conduit l Phone Line Monitoring TLM must be enabled l Phone Line trouble is ind...

Страница 30: ...cabinet LTE 3G HSPA PSTN AC Input AC Input PC4020 PC1864 PC1832 PC1616 RM1C ULC Relay LE4020 LE4020CF cabinet RM1C ULC Relay Note For PowerSeries NEO panel refer to Installation Guide 29005157 For Po...

Страница 31: ...PC1832 Only 3 2 DC IN AUX 2 3 1 COM 4 1 COM T1 R1 TIPRING 4 PGM ZONE Note Use EOL resistor in series with N O contacts of the relay connected to PGM4 Figure 1 10 Connection Details for Cellular Networ...

Страница 32: ...Use EOL resistor in series with N O contacts of the relay connected to PGM4 Figure 1 12 Connection Details for Cellular Network Supervision Relay Phone Line Supercision Relay and Redundant Fire Alarm...

Страница 33: ...evice Notice This equipment has been tested and found to comply with the limits for a Class B digital device pursuant to part 15 of the FCC Rules These limits are designed to provide reasonable protec...

Страница 34: ...The abbreviation IC before the registration number signifies that registration was performed based on a Declaration of Conformity indicating that ISED Canada technical specifications were met It does...

Страница 35: ...ll have cellular connection supervision enabled 3 The LE4020CF has its own power supply and the LE4020 shall be powered by ULC Listed Control Unit or power supply rated for the applic ation All interc...

Страница 36: ...f DSC You may not remove any proprietary notices marks or labels from the Software Product You shall institute reasonable measures to ensure compliance with the terms and conditions of this EULA Separ...

Страница 37: ...oftware license agreement included with the product The Customer assumes all responsibility for the proper selection installation operation and maintenance of any products purchased from DSC Custom pr...

Страница 38: ...product This disclaimer of warranties and limited warranty are governed by the laws of the province of Ontario Canada Digital Security Controls recommends that the entire system be completely tested...

Страница 39: ...ssively enforce its intellectual property rights to the fullest extent of the law including pursuit of criminal prosecution wherever necessary All trademarks not owned by Tyco are the property of thei...

Отзывы: