6.1 Wiring Diagrams

Note:

This product has been tested in accordance with UL 864 9th edition. According to this edition of the standard, the supervision window for reporting single-technology communicator trouble shall be set to five minutes.

However, the product can be installed in accordance with the requirements of NFPA72 2013 edition, which allows for a 60-minute supervision window.

Note:

Encryption shall be enabled for active communications.

Notes for using Private, Corporate and High Speed Data Networks:

Network access and domain access policies shall be set to restrict unauthorized

network access, and "spoofing" or "denial of service" attacks. Select the internet service providers that have redundant servers/systems, back-up power,

routers with firewalls enabled and methods to identify and protect against "denial of service" attacks (i.e., "spoofing").

For ULC Residential Fire and Burglary installations,

the LE4020/LE4020CF is listed as a sole means of communication or as a back up when used in

conjunction with a POTS line (dialer).

For UL Commercial Burglary installations

, the LE4020/LE4020CF is listed as a sole means of communication (supervision window of 200s required at

monitoring station) or as a back-up when used in conjunction with a POTS line (dialer). The LE4020CF has its own power supply and the LE4020 shall

be powered from any compatible listed control unit or com-patible listed power supply that complies with the ratings specified on page 1. The power

supply shall be lis-ted for burglary applications and provide a minimum of 4 hours standby power capabilities. An example of a suitable listed compatible

control unit is the DSC Model HS2128 with an AUX output rated 11.1 - 12.6VDC. An example of a suitable Listed power supply is DSC Model

HSM2204 with an AUX output rated 11.6 - 12.6VDC.

For ULC Commercial Fire Monitoring Installations,

the LE4020/LE4020CFcan be used in the following configurations:

1.

Active communication system with 180 seconds supervision and heartbeat sent to signal receiving center every 90 seconds (encryption shall be

enabled).

2.

Passive communication system in conjunction with a another communication path (e.g. DACT) (there is no heartbeat sent in this configuration,

only periodic test transmission ). Alarm signals must be sent simultaneously over both communication paths (Cellular and DACT). Every 24

hours, a test transmission must be sent to the signal receiving center over each communication path. Each communication path shall be mon-

itored for integrity (DACT shall have line monitoring enabled and LE4020/LE4020CF shall have cellular connection supervision enabled).

3.

The LE4020CF has its own power supply and the LE4020 shall be powered by ULC Listed Control Unit or power supply rated for the applic-

ation. All interconnections are restricted to same room, maximum 18 meters in metallic conduit.

For ULC Commercial Burglary Monitoring Installation

the LE4020/LE4020CF can be used in the following configurations:

1.

Active communication system with 180 seconds supervision and heartbeat sent to signal receiving centre every 90 seconds (encryption shall be

enabled).

2.

Passive communication system line security P1 (single communication channel) or line security P2 (used as backup in conjunction with another

communication path (e.g. DACT)). There is no heartbeat sent in this configuration, only periodic test transmissions. Every 24 hours, a test trans-

mission must be sent to the signal receiving centre over each communication path. Each communication path shall be monitored for integrity

(DACT shall have line monitoring enabled and LE4020/LE4020CF shall have cellular connection supervision enabled). For Level P2, the work-

ing communication path shall report the failure of the other channel within 240 seconds. The LE4020/LE4020CFcan be used in commercial burg-

lary applications up to Security Level IV.

For UL Commercial Fire Monitoring Installations, the LE4020/LE4020CF can be used in the following configurations:

1.

Standalone communicator, single communication technology - 5 minute supervision (heartbeat sent to supervising station every 90 seconds).

2.

Back-up communicator line for a DACT (dual communication technology, no heartbeat sent). Alarm signals must be sent first over the primary

communication path (DACT) and then, if this is known to have failed, over the secondary communication paths (other transmission tech-

nologies)

l

Primary: Compatible listed control unit's land line to central station (primary).

l

Secondary: LE4020/LE4020CF transmission through wireless network to central station.

Every 24 hours, a check-in signal must be sent to the central station over the primary dialer. The LE4020/LE4020CF sends a heartbeat test transmission to

the supervising station every 24 hours. Each communication path shall be monitored for integrity (DACT shall have line monitoring enabled and

LE4020/LE4020CF shall have cellular connection supervision enabled).

Power for model LE4020/LE4020CF shall be provided by one of the two compatible power supplies:

a.

Mircom Model – DTC-300A(W)(R), digital alarm communicator transmitter

b.

Simplex control panel 4100U with converter module 4100-5152 installed

Note:

Wiring between the LE4020/LE4020CF and FACP/Power Supply shall be made in the same room, in metal conduit and not longer than 20ft.

Note:

For LE4020CF, secondary power source must be installed.

Содержание LE4020

Страница 1: ...Communicator INSTALLATION MANUAL Warning This manual contains information on limitations regarding product use and function and information on the limitations as to liability of the manufacturer The...

Страница 2: ...inciples 15 5 1 Simulated Landline Mode 15 5 2 Panel Transmission Monitoring PTM 15 5 3 Cellular Communications Sequence 15 5 4 Inputs 16 5 5 Outputs 16 5 5 1 Activating the Outputs 16 5 6 Reporting C...

Страница 3: ...ling with regard to this lead acid battery Doing so will help protect the environment Some of the materials that are found within the battery could become toxic if not disposed of properly and may aff...

Страница 4: ...rmation that they have been received 1 1 Features l Dual band UMTS HSPA Penta Band LTE LE4020 LE4020CF l Advanced Carrier Selection l Bi color Wireless Signal Strength Indicator l LTE or 3G Internet c...

Страница 5: ...adapter Use internal PS4085 power supply module Without Battery 10 Vdc to 28 Vdc external power supply N A Battery Type sealed rechargeable type rated 12 V 7 Ah for 24 hr standby time plus 5 min alar...

Страница 6: ...and Rx LTE B2 1850 1910 MHz 1930 1990 MHz LTE B4 1710 1755 MHz 2110 2155 MHz LTE B5 824 849 MHz 869 894 MHz LTE B12 698 716 MHz 728 746 MHz LTE B13 777 787 MHz 746 756 MHz UMTS B2 1850 1910 MHz 1930 1...

Страница 7: ...3 4 5 6 1 4 3 7 8 9 10 11 12 Part Part 1 3G LTE antenna 7 Battery connector 2 Metal enclosure 8 Tamper switch 3 Status LEDs 9 Terminal blocks 4 Anchor screw holes 10 12 V 7Ah battery not included 5 S...

Страница 8: ...ich are not power limited Do not route any wiring over circuit boards Maintain at least 1 25 4mm separation A minimum 1 4 6 4mm of separation must be maintained at all points between Power Limited wir...

Страница 9: ...rews 2 Apply power DC and or battery The LE4020 LE4020CF is now in Placement Test mode Step 2 Determine Best Signal Location 1 Remove the screws and the front cover of the LE4020 LE4020CF metal enclos...

Страница 10: ...a carrier with a signal strength above 7 CSQ minimum of bottom signal strength LED on solid Red Blue Blue Green Top Blue Green Bottom FLASH ON OFF OFF OFF OFF FLASH ON OFF OFF OFF OFF FLASH ON OFF OFF...

Страница 11: ...ff Once the initialization sequence is complete the LE4020 LE4020CF switches to steady state operation Step 6 Mount the LE4020 LE4020CF 1 Power down the LE4020 LE4020CF by removing the DC power source...

Страница 12: ...e maximum current sink of each output must not exceed 50mA AUX 11 Auxiliary Output 9 to 14VDC Special Application Output 200 mA max for LE4020 and 100 mA max for LE4020CF Note Electrical current drawn...

Страница 13: ...so flashes once when the LE4020 LE4020CF transmits a signal and twice when it receives a kiss off from the central station Note If the LE4020 LE4020CF is programmed to be the primary communicator the...

Страница 14: ...1 OFF Wireless network trouble unable to connect to cellular network 2 OFF Battery trouble battery with low voltage output 3 OFF Input power trouble 1 Flashing Insufficient signal strength poor locat...

Страница 15: ...is in addition to the regular line voltage detection The LE4020 LE4020CF monitors the phone line for four consecutive failed attempts within a 12 minute win dow A failed attempt is assumed to have oc...

Страница 16: ...last format the control panel used to transmit an event 5 4 Inputs The LE4020 LE4020CF has four inputs that can be used to trigger specific communications These events trans mit using the Contact ID...

Страница 17: ...Restore Zone 2 Activation E12A 992 PA 992 YES Panic Alarm Zone 2 Restoral R12A 992 PH 992 YES Panic Alarm Restore Zone 3 Activation E13A 993 BA 993 YES Burglary Zone 3 Restoral R13A 993 BH 993 YES Bu...

Страница 18: ...with Swinger Shut down which limits certain trouble events to a maximum of four reports every 24 hours The condition restores and the counter resets at midnight Swinger Shutdown applies to the follow...

Страница 19: ...following troubles is present If the trouble occurs after the unit has processed the firmware update request the firmware update is not interrupted Input Power Trouble Low Battery Trouble 5 10 Low Po...

Страница 20: ...the PGM timer to a value between 1 and 255 seconds causes it to be timed The PGM activates for the programmed duration 2 Via C24 Communications program the phone number and access code used for SMS co...

Страница 21: ...ommands for the selected language 5 12 Phone Number Call Direction The PTM phone numbers to receiver group 1 or 2 are programmable The number programmed in the com municator must also be programmed as...

Страница 22: ...be programmed to communicate Contact ID or SIA over the telephone line Blue Green LED Status What it means CSQ Values Signal Strength Status Both Signal Strength LEDs ON Excellent Sig nal Strength 14...

Страница 23: ...charged to at least 12 5VDC If not wait at least 1 hour for the battery to charge l Remove the battery and measure the voltage the voltage should be at least 12VDC l Verify the input DC supply is rate...

Страница 24: ...nected l Verify correct phone line wiring l Ensure the Ringer Equivalency Number REN is not being exceeded on the line General Information Removing Connecting the antenna l To remove the antenna from...

Страница 25: ...ation must be maintained at all points between Power Limited wiring and all other Non Power Limited wiring Route wires as indicated in the diagram For UL Installations the system shall be installed in...

Страница 26: ...required for Fire Alarm Monitoring Refer to Fig 1 3 for wiring details Suggested compatible DACT models for use with LE4020CF are DSC models PC4020 with PC4701 Interface or PC5020CF with PC5700 Inter...

Страница 27: ...NNECT AC POWER TELEPHONE LINES PRIOR TO SERVICING These outputs shall be connected to zone inputs of an alarm control panel in order to provide the required trouble supervision visual and audible indi...

Страница 28: ...e mains plug and associated mains socket outlet is never obstructed The following wiring diagrams are examples of ULC Listed Fire Monitoring Installation connections Figure 1 6 Wiring Diagram for Fire...

Страница 29: ...separately listed power supply rated for the application 10 28V 700mA l All wiring connections must be run in a metallic conduit l Phone Line Monitoring TLM must be enabled l Phone Line trouble is ind...

Страница 30: ...cabinet LTE 3G HSPA PSTN AC Input AC Input PC4020 PC1864 PC1832 PC1616 RM1C ULC Relay LE4020 LE4020CF cabinet RM1C ULC Relay Note For PowerSeries NEO panel refer to Installation Guide 29005157 For Po...

Страница 31: ...PC1832 Only 3 2 DC IN AUX 2 3 1 COM 4 1 COM T1 R1 TIPRING 4 PGM ZONE Note Use EOL resistor in series with N O contacts of the relay connected to PGM4 Figure 1 10 Connection Details for Cellular Networ...

Страница 32: ...Use EOL resistor in series with N O contacts of the relay connected to PGM4 Figure 1 12 Connection Details for Cellular Network Supervision Relay Phone Line Supercision Relay and Redundant Fire Alarm...

Страница 33: ...evice Notice This equipment has been tested and found to comply with the limits for a Class B digital device pursuant to part 15 of the FCC Rules These limits are designed to provide reasonable protec...

Страница 34: ...The abbreviation IC before the registration number signifies that registration was performed based on a Declaration of Conformity indicating that ISED Canada technical specifications were met It does...

Страница 35: ...ll have cellular connection supervision enabled 3 The LE4020CF has its own power supply and the LE4020 shall be powered by ULC Listed Control Unit or power supply rated for the applic ation All interc...

Страница 36: ...f DSC You may not remove any proprietary notices marks or labels from the Software Product You shall institute reasonable measures to ensure compliance with the terms and conditions of this EULA Separ...

Страница 37: ...oftware license agreement included with the product The Customer assumes all responsibility for the proper selection installation operation and maintenance of any products purchased from DSC Custom pr...

Страница 38: ...product This disclaimer of warranties and limited warranty are governed by the laws of the province of Ontario Canada Digital Security Controls recommends that the entire system be completely tested...

Страница 39: ...ssively enforce its intellectual property rights to the fullest extent of the law including pursuit of criminal prosecution wherever necessary All trademarks not owned by Tyco are the property of thei...

Отзывы: