Rocket Installation and Operation Manual
8.2.2 Masonry Chimneys
The stove may also be connected to a
masonry
chimney,
provided
the
chimney complies with the construction
rules found in the building code
enforced locally. The chimney must
have either a clay liner or a suitably
listed stainless steel liner. If the
masonry chimney has a square or
rectangular liner that is larger in cross
sectional area than a round 6” flue, it
should be relined with a suitably listed
6” stainless steel liner. Do not
downsize the flue to less than 6” unless
the venting system is straight and
exceeds 25 feet in height.
passing through a combustible wall, the
use of an insulated listed thimble
required.
8.3 Minimum Chimney Height
The top of the chimney should be
tall enough to be above the air
turbulence caused when wind
blows against the house and its
roof. The chimney must extend at
least 1 m (3 ft.) above the highest
point of contact with the roof, and
at least 60 cm (2 ft.) higher than
any roof line or obstacle within a
horizontal distance of 3 m (10 f
8.4 The Relationship Between the Chimney and the House
Because the venting system is the engine that drives the wood heating system, it must
have the right characteristics. The signs of bad system design are cold backdrafting when
there is no fire in the stove, slow kindling of new fires, and smoke roll
opened for loading. There are two guidelines to follow. First, the chimney should be
installed up through the heated space of the house, not out and up an outside wall.
Second, the chimney should penetrate the top of the building at or near the highest heated
space.
Rocket Installation and Operation Manual
The stove may also be connected to a
masonry
chimney,
provided
the
chimney complies with the construction
rules found in the building code
enforced locally. The chimney must
have either a clay liner or a suitably
ess steel liner. If the
masonry chimney has a square or
rectangular liner that is larger in cross
sectional area than a round 6” flue, it
should be relined with a suitably listed
6” stainless steel liner. Do not
downsize the flue to less than 6” unless
venting system is straight and
exceeds 25 feet in height. When
passing through a combustible wall, the
an insulated listed thimble is
Minimum Chimney Height
The top of the chimney should be
tall enough to be above the air
caused when wind
blows against the house and its
roof. The chimney must extend at
least 1 m (3 ft.) above the highest
point of contact with the roof, and
at least 60 cm (2 ft.) higher than
any roof line or obstacle within a
horizontal distance of 3 m (10 ft.).
The Relationship Between the Chimney and the House
Because the venting system is the engine that drives the wood heating system, it must
have the right characteristics. The signs of bad system design are cold backdrafting when
the stove, slow kindling of new fires, and smoke roll-out when the door is
opened for loading. There are two guidelines to follow. First, the chimney should be
installed up through the heated space of the house, not out and up an outside wall.
chimney should penetrate the top of the building at or near the highest heated
35
Because the venting system is the engine that drives the wood heating system, it must
have the right characteristics. The signs of bad system design are cold backdrafting when
out when the door is
opened for loading. There are two guidelines to follow. First, the chimney should be
installed up through the heated space of the house, not out and up an outside wall.
chimney should penetrate the top of the building at or near the highest heated
Содержание Rocket DB03185
Страница 9: ...Rocket Installation and Operation Manual Rocket Installation and Operation Manual 9...
Страница 29: ...Rocket Installation and Operation Manual 29 Clearances to combustible materials and floor protection...
Страница 32: ...Rocket Installation and Operation Manual 32 Clearances for shield construction...
Страница 44: ...Rocket Installation and Operation Manual 44 Appendix 4 Exploded Diagram and Parts List...