background image

drive.web automation

Device Directory Window

  

Warning!

 

Changing  a  device  IP  address 

WILL

  disrupt  its 

network connections! If  a 

smarty

 is communicating with 

other  devices,  be  prepared  for  system  disruption.  In  the 

File 

menu  choose

  Utility  >  Remap  Export  File

  to 

remap a 

dw-system

 file with different IP address(es)

Select 

File

>

Administrate>Set IP Addresses for System

.   

smarty 

serial number is also its 

MAC Address

.  

Enter a valid IP address and click OK.   

An  icon  appears  with  IP  address  beneath.  Drive-dedicated 

models depict the actual frame size of  the drive. 

If  the icon at right appears, a network connection problem 

exists.  Check  connections,  LEDs,  and  that  the 

smarty

 

 

IP address is within the computer’s Ethernet subnet mask.   

Warning!

 

Importing  data  into  your 

smarty

  will  result  in 

immediate  execution  of   that  configuration. 

Dangerous 

Voltages and rotating machinery may result!

 Use 

a phantom to preview a configuration.

 

Directory > Import / Export Data.

 

All device configurations 

and connections in the directory in one 

.dw-system

 file.  

smarty

 

Icon Contextual Menu

  

Change Name

 - Name your 

smarty

 for easy identification.  

Import / Export Device Data...

 - Load / save configuration 

data to / from this 

smarty

 only. 

Unlock, Lock, Set Password

 

- Choose 

Restrict 

Modification

 to allow viewing the configuration, or 

Restrict All Access

Click the 

smarty

 icon

 to view the device configuration. 

Function Block Engine Window - FBE Menu 

(Standard 

savvy

, no 

SFD

Add function blocks in the order to be processed. Processing 

order is left to right, top to bottom. 

Click function blocks

 to view parameters and details.  

Connect between parameters

 and other 

drive.web

 devices.  

Warning!

 

Making  a  connection  results  in  immediate 

execution of  that connection. 

Dangerous Voltages and 

rotating machinery may result! 

Under the 

File

 menu, choose 

New Viewer...

 and then, 

File > Open Device Directory

.  

With two viewer windows, click a parameter, drag and 

drop onto a parameter in the other viewer.    

Parameter Contextual Menu

 - Data is formatted, limited, 

and scaled depending on the parameter. Use 

Get Info

 or 

Re-Scale...

 to verify or change.

 

Click parameters for the Setter Box

 - Increment, 

decrement, default, last state, or keyboard entry. 

Click blue connection block or arrow

 to jump to other end. 

smarty

 

HG503894Beta13

 

 

www.driveweb.com

              

              

Page 

#

/12

9

Apple, iOS, iPad, iPhone and iPod touch are trademarks of  Apple Inc., registered in the U.S. and other countries. 

App Store is a a service mark of  Apple Inc.

Содержание smarty dw240

Страница 1: ...kaging contain recyclable materials This device is designed to comply with Part 15 of the FCC Rules Operation is subject to the following two conditions 1 This device may not cause harmful interference and 2 this device must accept any interference received including interference that may cause undesired operation This Class A digital apparatus is designed to comply with Canadian ICES 003 Cet appa...

Страница 2: ...ROCUREMENT OF SUBSTITUTE GOODS OR SERVICES LOSS OF USE DATA OR PROFITS OR BUSINESS INTERRUPTION HOWEVER CAUSED AND ON ANY THEORY OF LIABILITY WHETHER IN CONTRACT STRICT LIABILITY OR TORT INCLUDING NEGLIGENCE OR OTHERWISE ARISING IN ANY WAY OUT OF THE USE OF THIS SOFTWARE EVEN IF ADVISED OF THE POSSIBILITY OF SUCH DAMAGE Product Identification smarty Cassette Models smarty is a programmable device ...

Страница 3: ...coder input 5 5VDC max 0 5VDC min 0 3VDC minimum differential Voltage Up to 1MHz ModbusRTU serial port is brought out to terminals instead of the jack in C2 smarty C4 Carrier 4 Ratings and Features adds to C3 Two 4 20mA current inputs Also 0 20mA 20 4mA and 20 0mA 100Ω input impedance Maximum input is 25mA 2 5VDC Six frequency event digital inputs 30Vmax 100kHz Replaces FT on C3 Seven frequency st...

Страница 4: ...n and blinks for activity 100BaseTX Green LED when 100BaseTX connection is made Carriers C1 and C2 Terminals and Dimensions smarty HG503894Beta13 www driveweb com Page 12 4 use in order only ctual size hite beyond 02441 for ol Gray 99 00mm Ref ue Drawing Title Drawn by Property of smarty front label art Ian Bardwell Jones Bardac Corp drive web smarty 100 1 2 PoE lOlOl r use in order only actual si...

Страница 5: ...V A B Carrier C3 Terminals and Dimensions Realtime Clock Battery CR2032 Realtime clock will be maintained for approximately 24hrs with no backup battery 4P4C XIO Port 8P8C CANopen Serial Port Width Overall 140mm 5 51 Height Overall 87mm 3 43 DINrail release clip Overall Height Back Panel to Front Panel 75mm 2 95 DI Digital Input DO Digital Output AO Analog Output AI Analog Input 1A Encoder 1 Chann...

Страница 6: ...5 TO7 0V 0V 0V 0V 0V 0V 0V 24V 0V 24V 0V A B 0V 1A 1A 1B 1B 0V 2A 2A 2B 2B Carrier C4 Terminals and Dimensions 4P4C XIO Port 8P8C CANopen Serial Port Width Overall 210mm 8 27 Height Overall 87mm 3 43 DI Digital Input DO Digital Output AO Analog Output AI Analog Input CI Current Input 1A Encoder 1 Channel A 1B Encoder 1 Channel B 1Z Encoder 1 Marker 5V 5VDC Power Output FI Frequency Input TPW Power...

Страница 7: ...o the unit depending on the installation Signal Wiring Notes Use twisted pair wiring for encoder and serial differential signals Outside metal enclosure use shielded cable with individually shielded twisted pairs such as Belden 8163 Ground shield at one end with a 360 ground clamp where cable enters quiet metal enclosure Separate wiring from AC power cables or RF noise sources smarty I O Functions...

Страница 8: ...s for each drive web device and the host computer For systems with more than one drive web device use an Ethernet switch for all drive web devices and computer Get started with savvy We strongly recommend attending our free online training seminars See page 12 We strongly recommend you read the User Manual and Getting Started Guides under the Help menu Use Create Phantom in the Directory menu to e...

Страница 9: ... Import Export Device Data Load save configuration data to from this smarty only Unlock Lock Set Password Choose Restrict Modification to allow viewing the configuration or Restrict All Access Click the smarty icon to view the device configuration Function Block Engine Window FBE Menu Standard savvy no SFD Add function blocks in the order to be processed Processing order is left to right top to bo...

Страница 10: ...n blocks and connections is at the left of the Signal Flow Diagram showing program execution order from top down Change execution order by dragging function blocks up or down the list In this picture ENC1 Speed function block is moved so that it is processed after ENC Phase Lock savvyPanel Operator Station Computers Apple mobile digital devices iPad iPhone and iPod Touch are operator touch station...

Страница 11: ... in Java based savvyPanel Appears as graphic tile in iOS Function blocks enable savvyPanel actions Alarm Annunciator Provides a system wide alarm annunciation when active Touch to view page 255 Presence Monitor Indicates the presence of a tagged savvyPanel application viewing a particular page Latch and SR Latch For lighted start stop pushbuttons Setpoint Monitor Adjust meter and setter range Dual...

Страница 12: ...t write or force parameters that are read only or have incoming drive web connections Click the Comms Server icon in the FBE or SFD view dwOption 04 ModbusTCP IP slave server Supported Modbus Function Codes 1 thru 6 15 and 16 Supports up to five simultaneous clients masters dwOption 25 EIP PCCC Server Supports PLC5 Typed Write and Typed Read commands See Appendix B of the savvy User Manual for inf...

Отзывы: