INSTALLATION

Figure 5-1: Single-Tube

Mounting dispersion tube without
condensate drain

• Connection can be made to the humidifier

with vapor hose or hard piping.

• Hard piping should have a minimum

I.D. of 1½" (DN40).

• A minimum pitch of 2"/foot (15%) back to

the humidifier should be maintained.

• Short sweep 90° elbows are not

recommended; use two 45° elbows
12" (300 mm) apart or long sweep 90°
elbows instead.

• Thin-walled tubing will heat up faster than

heavy-walled pipe, causing less steam
loss at start-up.

• Insulating hard piping will reduce the steam

output loss caused by condensation.

• When mounting the humidifier above the

level of dispersion tube, see Figure 4-2 on
Page 4.

Mounting dispersion tube with
condensate drain

• Mount dispersion tube level.
• Orient dispersion tube so that tubelets are

pointed straight up.

• The dispersion tube must be pitched a

minimum of 1/8"/ft (1%) back to the
humidifier when using a condensate drain.

• Condensate drain tubing must be

pitched a minimum of 1/4"/ft (2%) back
to the humidifier.

• Condensate drain is not provided when

steam flow is 34 lbs/hr (15 kg/hr) or less.

Figure 5-2: RAPID-SORB

®

 with condensate wasted to floor drain

Notes:

*

When steam flow is 34 lbs/hr (kg/hr) or less, condensate drain tubing is not provided
by DRI-STEEM. A minimum pitch of 2"/ft (15%) back to the humidifier must be

maintained in the dispersion tube when there is no separate condensate drain.

**

Condensate drain tubing material must be suitable for 212 °F (100 °C) water.

OM-351-1

Movable duct plate (can be mounted
within limits of 2.5" [65 mm]).

3.25"

(85 mm)

1/4"/ft (2%) pitch

1/8"/ft (1%) pitch

2"/ft (15%) pitch

Insertion length

3.25"

OM-224-s

1 1/2" (DN40)

vapor hose

 or rigid piping

Failing to follow these recommendations may
result in excessive back pressures being
imposed on the humidifier. This may lead to
dispersion tube(s) spitting, steam blowing
through water seals, or leaking gaskets.
When the distance between humidifier and
the dispersion tube(s) exceeds 20 feet (6 m),
consult factory for recommendations.

3.25"

(85 mm)

3.25

"

(85 mm

)

3.25

"

(85 mm

)

2.5"

(65 mm)

3.25

"

(85 mm

)

3.25"

(85 mm)

Mounting

nut

Mounting nut

High temperature resin tubelets

1/2" O.D. (DN15) stainless steel

(condensate drain)*

1/4" NPT

(DN8) coupling*

Mounting a RAPID-SORB
dispersion panel

For RAPID-SORB mounting dimensions,
please see the drawing at right.

Dispersion tube

Orificed tubelets

Air gap

5" (125 mm) min

.

6" (150 mm) min.

Mounting bracket

Escutcheon plate

Air flow

Duct

Slip coupling or hose cuff

Pitch 1/8" per foot
(1%) (minimum)

Header

1"x1.5" SST channel

Open drain

¾" (DN20)

condensate drain**

 tube by others

High temperature 

 

resin tubelets

Insertion length

2.5"

(65 mm)

VMOM-0600.PDF   5

11/19/2009   9:59:10 AM

Содержание VAPORMIST

Страница 1: ...AND SAVE THESE INSTRUCTIONS VAPORMIST and VAPORMIST DI ELECTRIC STEAM HUMIDIFIERS Installation Operation and Maintenance Manual For toll free technical support call 1 800 328 4447 cETL LISTED ETL LIS...

Страница 2: ...s DRI STEEM Humidifier Company VAPORMIST and VAPORMIST DI humidifiers 3 Installation Locating and mounting the VAPORMIST humidifier 4 Examples of mounting the dispersion tube 4 Mounting dispersion tub...

Страница 3: ...INCOLOY alloy sheathed immersion heaters Keyholes for wall mounting Water fill NPT DN8 female 1 DN40 or 2 DN50 flexible vapor hose connects to dispersion tube in duct Condensate return line Duct Elect...

Страница 4: ...in duct Vapor hose and dispersion tube s should be pitched back to the humidifier with a minimum gradual slope of 2 per foot 15 A single dispersion tube cannot be used with VM 30 or VM 34 Figure 4 2...

Страница 5: ...ondensate drain tubing is not provided by DRI STEEM A minimum pitch of 2 ft 15 back to the humidifier must be maintained in the dispersion tube when there is no separate condensate drain Condensate dr...

Страница 6: ...drain pipes into a single drain line may result in the backflow of drain water into the humidifier cabinet causing the unit to malfunction All wiring must be in accordance with all governing codes and...

Страница 7: ...6 mm 2 25 57 mm Top view Back of enclosure Front of enclosure OM 282 1 Power wire knockout Humidistat or SDU knockouts 24 19 614mm 3 4 NPT DN20 tankdrain 3 4 NPT DN20 framedrain Model number Steam cap...

Страница 8: ...re it disappears it could collect and drip as water The greater the space relative humidity the more the fog will rise throw and spread before disappearing The dis tances the fog travels before it dis...

Страница 9: ...SDU E mechanical detail OM 54 1 2 25 57 mm Steam inlet Steam outlet If the SDU E or SDU I is immediately above the VAPORMIST disconnect both hose clamps on the steam hose grip the hose and rotate it t...

Страница 10: ...that proper grounding and an approved earth groundareprovided 2 Confirm that the control signal being connected to the VAPOR LOGIC3 system is compatible with the VAPOR LOGIC3 program Identify the VAP...

Страница 11: ...the electrical panel cover or heater terminal cover until electrical power is disconnected Safety first If the VAPORMIST has an SDU mounted directly above it the SDU cover must be removed before remov...

Страница 12: ...tank to drain completely Disconnect the fill line at the fill fitting Disconnect the electrical plugs between the tank components and the back of the electrical panel includes power plug low water sw...

Страница 13: ...control voltage across the fill valve output Humidifier does not stop filling Lack of tank to probe electrical continuity Water conductivity must be 100 micromhos cm 2 gr gal or 34 2 mg liter Add sal...

Страница 14: ...oning float switch Check to make sure that float moves freely on stem Plugged fill valve Check fill valve inlet Humidifier does not stop filling Open drain valve Obstruction in drain valve will not al...

Страница 15: ...ack 4 409593 002 No Description Qty Part No 1 Subpanel VM99 barrier 1 120801 2 Ground lug L 35 10 14 GA CP 8 1 409250 017 2 Ground lug L 70 6 8 GA CP 4 1 409250 018 3 Transformer 600V 1 408896 3 Trans...

Страница 16: ...on pages 17 and 18 VM Model VMDI Model 3 1 2 19 25 6 7 34 8 34 22 24 28 20 15 16 11 33 32 31 10 18 25 9 4 5 13 35 36 12 15 11 27 20 16 17 29 30 23 21 26 25 37 3 4 NPT frame drain male Tank drain Hole...

Страница 17: ...05390 006 5 Hose cuff 2 ID VM 21 34 1 305391 006 6 Cover tank 1 7 Heater element 8 Probe assembly cord and plug 1 406050 005 9 Probe assembly gasket 1 309750 004 10 Probe assembly VM 2 4 1 406270 10 P...

Страница 18: ...pter VM 6 16 1 160224 041 22 Fill adapter VM 21 34 1 160224 052 23 Panel insulation 1 309845 003 24 Sensor temperature 1 405760 25 Screw Phillips head 8 32 x 8 700170 007 26 Frame assembly chassis 1 1...

Страница 19: ...mer 600V 1 408986 3 Transformer 120 208 240 480 1 408965 001 4 Channel wire with cover 2 408999 003 5 Main board VL 3 1 408490 001 6 Keypad board VL 3 1 408490 002 7 Plug 4 prong female 4 409585 008 8...

Страница 20: ...irect associated with the installation removal or reinstallation of any defective product DRI STEEM s limited warranty shall not be effective or actionable unless there is compliance with all installa...

Отзывы: