3
Figure 3-2: VAPORMIST DI humidifier
(deionized water)
The VAPORMIST DI humidifier shown here is specifically designed for use with deionized or reverse osmosis water.
Figure 3-1: VAPORMIST humidifier
(standard water)
The standard VAPORMIST unit requires water conductivity of at least 100 micromhos/centimeter (2 grains per gallon)
to operate. It will not operate with water treated by reverse osmosis or deionization processes. (See DI model below.)
VAPORMIST
®
HUMIDIFIER
Removable
evaporating chamber
Slide assembly under evaporating chamber
provides easy removal for cleaning
INCOLOY alloy-sheathed immersion heaters
Keyholes for wall mounting
Water fill ¼" NPT
(DN8) (female)
1½" (DN40) or 2" (DN50)
flexible vapor hose connects
to dispersion tube in duct
Condensate return line
Duct
Electrical side
Electrical connections
¾" NPT (DN20) coupling,
skimmer port and overflow drain
Water fill access hole
OM-82-4
OM-82-5
Electrical side
Condensate return line
INCOLOY alloy-sheathed immersion heaters
Removable
evaporating chamber
Slide assembly under evaporating chamber
provides easy removal for cleaning
Water fill access hole
Keyholes for wall mounting
Water fill ¼" NPT
(DN8) (female)
1½" (DN40) or 2" (DN50) flexible vapor
hose connects to dispersion tube in duct
Duct
Electrical connection
Float cutoff switch
Ball valve
¾" NPT (DN20) coupling,
skimmer port and overflow drain
VMOM-0600.PDF 3
11/19/2009 9:59:10 AM