MAINTENANCE

The best way to determine how often your particular
system will need maintenance is to remove the cover and
inspect it after its first three months of duty. Potable
water carries a variety of minerals and other materials in
a mix that varies from location to location. This variation
in water quality, combined with hours of operation and
duty cycle, will determine your own unique maintenance
schedule.

Water quality makes a difference

1.

Light to moderately hard water (2 to 10 grains
hardness per gallon) requires:

annual cleaning

regular skimming

2.

High mineral content water (more than 10 grains
hardness per gallon) requires:

cleaning frequency determined by use and
water quality

regular skimming

periodic drain and flush cycles

3.

DI/RO water (Model VMDI) requires:

no regular cleaning (although regular
inspections are advised)

no regular skimming or drain and flush cycles

regular verification that water processing
equipment is operating correctly. The
presence of chlorides in improperly
processed DI water will eventually cause
pitting and failure of the tank and its
components.

4.

To dramatically reduce mineral accumulation inside
the evaporating chamber, softening of the makeup
water is recommended. (Solids, like silica, are not
removed in the softening process.)

Standard water models (VAPORMIST

®

)

Proper skimming, draining and flushing

1.

Skimming will remove most water impurities at the
surface, ensuring proper surface tension and an
even boil. Skimming will remove most entrained
contaminants that have not yet precipitated as scale.

2.

Draining and flushing will completely remove
entrained contaminants and assist in removing
precipitated contaminants like scale and silica.

To inspect and service

1.

Remove the evaporating chamber:

Remove the two fasteners on each side of the
cover enclosure.

Remove the enclosure.

Do not remove the electrical panel cover or
heater terminal cover until electrical power
is disconnected. Safety first.

If the VAPORMIST has an SDU mounted
directly above it, the SDU cover must be
removed before removing the unit cover.

If the tank is hot, cool it down by moving the
valve lever located on the back of the drain
valve to the manual open position – the fill valve
will eventually open allowing cool water to run
through the tank until it is cool enough to
handle.

Shut off the water supply.

Shut off the electrical supply.

Allow the tank to completely drain.

Disconnect the fill line at the supply side of the
fill valve.

Disconnect the electrical plugs between the
tank components and the back of the
electrical panel (includes: power plug, fill
plug, drain plug, water level control plug, tank
temperature sensor plug and thermal trip
plug).

DISCONNECT BY PULLING ON

PLUG HOUSING. DO NOT DISCONNECT
BY PULLING ON CORD OR WIRES.

Disconnect the drain union on the back left
corner of the frame.

Disconnect the steam supply hose from the top
of the tank.

Lift the tank foot above the frame flange and
slide the tank assembly forward to remove.

2.

Loosen the four cover bolts and remove the cover
assembly from the tank.

3.

Clean the tank interior using a putty knife or similar
flat instrument.

4.

Unplug probe plug assembly. Leave ground wire
connected to tank. Unscrew the probe rod assembly
and clean the plastic probe housing, ensuring that all
passageways are clear. Clean the probe rods using
steel wool or a similar mild abrasive material. Inspect
the composite plastic probe housing for any signs of
cracking, roughness, or deterioration and replace if
needed.

5.

Install the probe and probe plug assembly. Verify
ground wire.

6.

Secure the chamber cover, making sure the cover
gasket is seated and the chamber is sealed.

7.

Reinstall the evaporating chamber:

Reconnect the fill line.

Reconnect the electrical plugs.

Reconnect the drain union.

Reconnect the vapor hose.

8.

Move the drain valve lever back to the auto position.

9.

Turn on the water supply.

10. Turn on the electrical power.

VMOM-0600.PDF   11

11/19/2009   9:59:11 AM

Содержание VAPORMIST

Страница 1: ...AND SAVE THESE INSTRUCTIONS VAPORMIST and VAPORMIST DI ELECTRIC STEAM HUMIDIFIERS Installation Operation and Maintenance Manual For toll free technical support call 1 800 328 4447 cETL LISTED ETL LIS...

Страница 2: ...s DRI STEEM Humidifier Company VAPORMIST and VAPORMIST DI humidifiers 3 Installation Locating and mounting the VAPORMIST humidifier 4 Examples of mounting the dispersion tube 4 Mounting dispersion tub...

Страница 3: ...INCOLOY alloy sheathed immersion heaters Keyholes for wall mounting Water fill NPT DN8 female 1 DN40 or 2 DN50 flexible vapor hose connects to dispersion tube in duct Condensate return line Duct Elect...

Страница 4: ...in duct Vapor hose and dispersion tube s should be pitched back to the humidifier with a minimum gradual slope of 2 per foot 15 A single dispersion tube cannot be used with VM 30 or VM 34 Figure 4 2...

Страница 5: ...ondensate drain tubing is not provided by DRI STEEM A minimum pitch of 2 ft 15 back to the humidifier must be maintained in the dispersion tube when there is no separate condensate drain Condensate dr...

Страница 6: ...drain pipes into a single drain line may result in the backflow of drain water into the humidifier cabinet causing the unit to malfunction All wiring must be in accordance with all governing codes and...

Страница 7: ...6 mm 2 25 57 mm Top view Back of enclosure Front of enclosure OM 282 1 Power wire knockout Humidistat or SDU knockouts 24 19 614mm 3 4 NPT DN20 tankdrain 3 4 NPT DN20 framedrain Model number Steam cap...

Страница 8: ...re it disappears it could collect and drip as water The greater the space relative humidity the more the fog will rise throw and spread before disappearing The dis tances the fog travels before it dis...

Страница 9: ...SDU E mechanical detail OM 54 1 2 25 57 mm Steam inlet Steam outlet If the SDU E or SDU I is immediately above the VAPORMIST disconnect both hose clamps on the steam hose grip the hose and rotate it t...

Страница 10: ...that proper grounding and an approved earth groundareprovided 2 Confirm that the control signal being connected to the VAPOR LOGIC3 system is compatible with the VAPOR LOGIC3 program Identify the VAP...

Страница 11: ...the electrical panel cover or heater terminal cover until electrical power is disconnected Safety first If the VAPORMIST has an SDU mounted directly above it the SDU cover must be removed before remov...

Страница 12: ...tank to drain completely Disconnect the fill line at the fill fitting Disconnect the electrical plugs between the tank components and the back of the electrical panel includes power plug low water sw...

Страница 13: ...control voltage across the fill valve output Humidifier does not stop filling Lack of tank to probe electrical continuity Water conductivity must be 100 micromhos cm 2 gr gal or 34 2 mg liter Add sal...

Страница 14: ...oning float switch Check to make sure that float moves freely on stem Plugged fill valve Check fill valve inlet Humidifier does not stop filling Open drain valve Obstruction in drain valve will not al...

Страница 15: ...ack 4 409593 002 No Description Qty Part No 1 Subpanel VM99 barrier 1 120801 2 Ground lug L 35 10 14 GA CP 8 1 409250 017 2 Ground lug L 70 6 8 GA CP 4 1 409250 018 3 Transformer 600V 1 408896 3 Trans...

Страница 16: ...on pages 17 and 18 VM Model VMDI Model 3 1 2 19 25 6 7 34 8 34 22 24 28 20 15 16 11 33 32 31 10 18 25 9 4 5 13 35 36 12 15 11 27 20 16 17 29 30 23 21 26 25 37 3 4 NPT frame drain male Tank drain Hole...

Страница 17: ...05390 006 5 Hose cuff 2 ID VM 21 34 1 305391 006 6 Cover tank 1 7 Heater element 8 Probe assembly cord and plug 1 406050 005 9 Probe assembly gasket 1 309750 004 10 Probe assembly VM 2 4 1 406270 10 P...

Страница 18: ...pter VM 6 16 1 160224 041 22 Fill adapter VM 21 34 1 160224 052 23 Panel insulation 1 309845 003 24 Sensor temperature 1 405760 25 Screw Phillips head 8 32 x 8 700170 007 26 Frame assembly chassis 1 1...

Страница 19: ...mer 600V 1 408986 3 Transformer 120 208 240 480 1 408965 001 4 Channel wire with cover 2 408999 003 5 Main board VL 3 1 408490 001 6 Keypad board VL 3 1 408490 002 7 Plug 4 prong female 4 409585 008 8...

Страница 20: ...irect associated with the installation removal or reinstallation of any defective product DRI STEEM s limited warranty shall not be effective or actionable unless there is compliance with all installa...

Отзывы: