64
Operation
Operation:
Troubleshooting guide
Troubleshooting guide.
Problem
number
Problem
Possible cause
Action
19
20
21
EEPROM fault
Flue fault
Burner No. fault
Internal program
changed
(VAPOR-LOGIC
3
detected a change
from its previous
program check)
The combustion air
damper is incorrectly
wired or has failed to
open.
The power vent
pressure switch is
incorrectly wired or
the power vent has
failed to start.
No gas supply to unit
Gas valve is off or
there is no power to
the valve.
Broken ignitor
Gas valve/ignitor/
sensing electrode is
out of sequence
Gas valve outlet
pressure is too low.
Blower inlet is dirty
or obstructed.
Consult DRI-STEEM for
reprogramming instructions.
Check for proper combustion air
damper wiring.
Check for proper power vent wiring.
Verify that gas service valve is on and
receiving minimum pressure to
manifold per rating plate.
Verify that valve is in on position
and that there is power to the valve.
Verify that ignitor glows.
Verify wire connections to these
components.
Verify out pressure is set per rating
plate.
Clean inlet and check for obstructions.
More on next page ...
VL3-IOM-0301-METRIC.pdf 68
11/19/2009 9:22:40 AM