8
Program code nomenclature.
Product overview
Product overview:
Program code nomenclature
Program code explained
A 14-digit VAPOR-LOGIC
®
3
program code appears on
the front of the control cabinet and on the wiring
diagram inside the control cabinet. The program code
specifies the parameters of the VAPOR-LOGIC
3
microprocessor, which controls your humidification
system. An explanation of the program code is detailed
below.
VAPOR-LOGIC
3
program code
A. Type of units:
E = English
M= Metric
B. VAPOR-LOGIC
3
system type:
G = GTS
®
S = STS
®
L = LTS
®
V = VAPORSTREAM
®
M = HUMIDI-TECH
®
C = CRUV
®
U = ULTRA-FOG
®
N = Steam Injection
C. VAPOR-LOGIC
3
board classification:
1 = One-tank system
2 = Two-tank system
3 = Three-tank system
4 = Four-tank system
5 = Five-tank system
6 = Six-tank system
D. Digital display/keypad features:
1 = Single keypad
E. Type of outputs (0-4):
0 = Steam valve/100% SSR
1 = One heat stage
2 = Two heat stages
3 = Three heat stages
4 = Four heat stages
F. System kilograms output:
##### = Output capacity
(e.g., 00128 = output capacity in kg/hr)
G. Type of water level control:
D = DI w/ manual drain
E = DI w/ end of season drain
M = Standard w/ manual drain
A = Standard w/ autodrain
H. Operating mode:
1 = Single staged
2 = Externally staged
6 = GTS
7 = TP
8 = SSR
9 = Steam valve
I. VAV options:
V = Option present
O = Option not selected
S = SDU option
J. Temperature compensation options:
T = Option present
O = Option not selected
K. Type of humidity sensing device:
N = None, for on/off
C = 0-135 Ohm humidistat
D = 6-9 VDC humidistat
H = 0-10 VDC humidistat
E = 4-20 mA humidistat
X = 4-20 mA transmitter
Q = Dew point transmitter
S = Special