ULTRA-SORB MODEL MP INSTALLATION, OPERATION, AND MAINTENANCE MANUAL
Piping
Table 16-2:
Steam loss of interconnecting steam hose or tubing
Description
Nominal hose or tubing size
Steam loss
Insulation thickness
Noninsulated
Insulated
inches
DN
lbs/hr/ft
kg/h/m
lbs/hr/ft
kg/h/m
inches
mm
Hose
1½
40
0.15
0.22
N/A
N/A
N/A
N/A
2
50
0.20
0.30
N/A
N/A
N/A
N/A
Tubing
1½
40
0.11
0.16
0.020
0.030
2.0
50
2
50
0.14
0.21
0.025
0.037
2.0
50
3
80
0.20
0.30
0.030
0.045
2.5
64
4
100
0.26
0.39
0.030
0.045
3.0
76
5
125
0.31
0.46
0.035
0.052
3.0
76
6
150
0.36
0.54
0.039
0.058
3.0
76
Note: Data based on an ambient air temperature of 80 °F (27 °C), fi berglass insulation, and copper tubing.
mc_051310_1216
Table 16-1:
Maximum steam carrying capacity and length of interconnecting steam hose or tubing
Steam hose
1
Copper or stainless steel tubing
Hose I.D.
Maximum capacity
Maximum length
2
Tubing size
Maximum capacity
3
Maximum developed
length
4
inches
DN
lbs/hr
kg/h
ft
m
inches
DN
lbs/hr
kg/h
ft
m
1½
40
150
68
10
3
1½
40
150
68
20
6
2
50
250
113
10
3
2
50
220
100
30
9
1. Use DriSteem steam hose for best results. Other hose may have shorter
life and may cause foaming in the evaporating chamber resulting in
condensate discharge at the dispersion assembly. Do not use steam
hose for outdoor applications.
2. Maximum recommended length for steam hose is 10' (3 m). Longer
distances can cause kinking or low spots.
3
5
80
5
450
204
80
24
4
5
100
5
750
340
100
30
5
5
125
5
1400
635
100
30
6
5
150
5
2300
1043
100
30
3. Insulate tubing to minimize loss of capacity and effi ciency.
4. Developed length of tubing equals measured length plus 50% of
measured length, to account for fi ttings.
Longer tubing lengths are possible at capacities lower than listed
maximums. Consult factory.
5. Requires fl ange connection.
Note: Capacities and lengths in this table are for steam from a nonpressurized steam humidifi er to a nonpressurized steam dispersion panel, and are
based on total maximum pressure drop in hose or tubing of 5" wc (1250 Pa).
mc_091410_1050-LVLH