Table 6-1:
Troubleshooting guide

Issue

Power failure

Check for proper supply voltage.
Check for wiring shorts; reset breaker.

Error message

Err1: 

An assigned input is not enabled or missing. All control loops, functions, 

and outputs tied to this input will be disabled. Verify input connections, jumper 

settings and parameter settings for the input involved.

Err3:

 A function refers to a disable input. Disable the function or enable the 

input.

Err4:

 Internal failure. Product must be replaced.

Table 6-2:
Replacement parts

Model

Description

Part Number

TCI-W11-U-W26 kit 1 Model TCI-W11-U-W26, 1 duct sensor

600968

TCI-W11-U-W26

PI-controller, wall flush mounted int. 1 UI, 1 AO, 

default: 0-10V input remote RH, 0-10V output 

humidify

600966

TCI-W11-U-H-W24

PI-controller, wall flush mounted int. 1 UI, 1 AO, 

int. humidity sensor 3% accuracy, default: humidity 

control, int. RH, 0-10V output

600965

Accessories

Duct sensor, 3% 0 - 10V

600967

AES1-HT-A2

RH sensor 2%

600983

AES1-HT-A3

RH sensor 3%

600982

Содержание TCI-W11-U

Страница 1: ...ious injury from electrical shock or damage to product and can void product warranty due to possible product misapplication CAUTION 1 Do not set humidity higher than recommended or moisture can accumulate which can cause bacteria and mold growth or dripping water into building spaces Dripping water can cause property damage bacteria and mold growth can cause illness 2 Do not set humidity up to rec...

Страница 2: ...umidity default disabled Set min or max humidity display default 0 and 100 Calibrate sensor Tune the PI control loop Enable security to prevent user from changing parameters WARNING This device is intended to be used for comfort applications Where a device failure endangers human life and or property it is the responsibility of the owner designer and installer to add additional safety devices to p...

Страница 3: ... to EN60730 1 Environment Operation To IEC 721 3 3 Climatic conditions class 3K5 Temperature 0 to 50ºC 32 to 122ºF Humidity 95 RH non condensing Transport storage To IEC 721 3 2 and IEC 721 3 1 Climatic conditions class 3K5 and class 1K3 Temperature 25 to 70ºC 13 to 158ºF Humidity 95 RH non condensing Mechanical conditions class 2M2 Standards conformity EMC standard low voltage directive 2014 30 E...

Страница 4: ...RE 4 1 USING THE DRISTEEM HUMIDISTAT DISPLAY Down Decrease SET POINT Parameter setting SCROLL menu options and parameters Off Energy hold off Outputs are off inputs monitored for alarms Up Increase SET POINT Parameter setting SCROLL menu options and parameters DISPLAY INPUT VALUES 75 UI1 For TCI W11 Press OPTION 2 s SEL and H C is displayed Press UP key once UI1 and its value are displayed UI1 is ...

Страница 5: ... set correctly 4 Slide the two latches located on the top of the front part into the hooks at the upper side of the mounting plate 5 Carefully lower the front part until the interconnector reaches the mounting plate Continue pressing in a gentle way until the front part is fully connected While inserting the connectors a slight resistance can be felt This is normal Do not use excessive force 6 Wit...

Страница 6: ...ts tied to this input will be disabled Verify input connections jumper settings and parameter settings for the input involved Err3 A function refers to a disable input Disable the function or enable the input Err4 Internal failure Product must be replaced Table 6 2 Replacement parts Model Description Part Number TCI W11 U W26 kit 1 Model TCI W11 U W26 1 duct sensor 600968 TCI W11 U W26 PI controll...

Отзывы: