background image

3

DRISTEEM TCI-W11  HUMIDISTAT INSTALLATION MANUAL

Table 3-1:
TCI-W11 specifications

Power Supply

Power requirements

24 VAC ±10%, 50/60 Hz, Class 2, 2.0A, 48 VA max.

24 VDC ±10%

Power consumption

Maximum 3 VA

Electrical connection

Terminal connectors

0.34 - 2.5 mm

2

 wire (AWG 22 - 13)

Signal Inputs

Universal input

Setting for voltage or current

Input signal

0 - 10 V or 0 - 20 mA

Resolution

9.76 mV or 0.019 mA (10 bit)

Impedance

Voltage: 98kΩ

Current: 240Ω

Humidity sensor AEs3-HT-Ax

Capacity sensor

Range

0 - 100% rH

Measuring accuracy

See Figure 4.2.

Hysteresis

±1%

Repeatability

±0.1%

Stability

<0.5% / year

Signal Outputs

Analog output

Output signal

DC 0 to 10V/0 to 20mA

Resolution

9.76 mV / 0.019 mA

Maximum load

Voltage: 5kΩ

Current: 250Ω

Insulation strength between relays contacts and system electronics

2000 VAC to EN60730-1

Environment

Operation

To IEC 721-3-3

Climatic conditions

class 3K5

Temperature

0 to 50ºC (32 to 122ºF)

Humidity

< 95% RH non-condensing

Transport & storage

To IEC 721-3-2 and IEC 721-3-1

Climatic conditions

class 3K5 and class 1K3

Temperature

-25 to 70ºC (-13 to 158ºF)

Humidity

< 95% RH non-condensing

Mechanical conditions

class 2M2

Standards

conformity, EMC standard, low voltage directive

2014/30/EU

2014/35/EU

Product standards

Automatic electrical controls for household and similar use

EN 60730-1

Special requirement on temperature dependent controls

EN 60730-2-9

Degree of protection

IP30 to EN 60529

Pollution class

II (EN 60730-1)

Safety class

III (IEC60536)

Overvoltage category

I (EN60730-1)

General

Material: Cover, back part, mounting plage

Fire proof ABS plastic (UL94 class V-0)

Galvanized steel

Dimensions (H x W x D)

Front part: 15 X 113 X 72 mm (0.6 X 4.5 X 2.8in)

Power case: ø58 x 32 mm (ø2.3" x 1.3")

RoHS compliant according to 

2011/65/EU

Weight (including package)

TCI-W11 = 253 g (8.9 oz)

Содержание TCI-W11-U

Страница 1: ...ious injury from electrical shock or damage to product and can void product warranty due to possible product misapplication CAUTION 1 Do not set humidity higher than recommended or moisture can accumulate which can cause bacteria and mold growth or dripping water into building spaces Dripping water can cause property damage bacteria and mold growth can cause illness 2 Do not set humidity up to rec...

Страница 2: ...umidity default disabled Set min or max humidity display default 0 and 100 Calibrate sensor Tune the PI control loop Enable security to prevent user from changing parameters WARNING This device is intended to be used for comfort applications Where a device failure endangers human life and or property it is the responsibility of the owner designer and installer to add additional safety devices to p...

Страница 3: ... to EN60730 1 Environment Operation To IEC 721 3 3 Climatic conditions class 3K5 Temperature 0 to 50ºC 32 to 122ºF Humidity 95 RH non condensing Transport storage To IEC 721 3 2 and IEC 721 3 1 Climatic conditions class 3K5 and class 1K3 Temperature 25 to 70ºC 13 to 158ºF Humidity 95 RH non condensing Mechanical conditions class 2M2 Standards conformity EMC standard low voltage directive 2014 30 E...

Страница 4: ...RE 4 1 USING THE DRISTEEM HUMIDISTAT DISPLAY Down Decrease SET POINT Parameter setting SCROLL menu options and parameters Off Energy hold off Outputs are off inputs monitored for alarms Up Increase SET POINT Parameter setting SCROLL menu options and parameters DISPLAY INPUT VALUES 75 UI1 For TCI W11 Press OPTION 2 s SEL and H C is displayed Press UP key once UI1 and its value are displayed UI1 is ...

Страница 5: ... set correctly 4 Slide the two latches located on the top of the front part into the hooks at the upper side of the mounting plate 5 Carefully lower the front part until the interconnector reaches the mounting plate Continue pressing in a gentle way until the front part is fully connected While inserting the connectors a slight resistance can be felt This is normal Do not use excessive force 6 Wit...

Страница 6: ...ts tied to this input will be disabled Verify input connections jumper settings and parameter settings for the input involved Err3 A function refers to a disable input Disable the function or enable the input Err4 Internal failure Product must be replaced Table 6 2 Replacement parts Model Description Part Number TCI W11 U W26 kit 1 Model TCI W11 U W26 1 duct sensor 600968 TCI W11 U W26 PI controll...