18
HUMIDI-TECH
®
DISPERSION
Steam loss of interconnecting vapor hose, tubing and pipe
Notes:
This data is based on an ambient air temperature of 27 °C, fiberglass insulation, copper tubing, and Schedule 40 pipe.
Maximum steam carrying capacity and length of
interconnecting vapor hose, tubing and pipe*
Notes:
* Based on total maximum pressure drop in hose, tubing or piping of 1250 Pa
** Maximum recommended length for vapor hose is 3 m. Longer distances may cause kinking or low spots.
*** To minimize loss of capacity and efficiency, insulate tubing and piping.
Developed length equals measured length plus 50% of measured length, to account for pipe fittings.
Vapor hose
Copper or stainless steel tubing
and Schedule 40 steel pipe
Hose I.D.
(DN)
Maximum
capacity
(kg/h)
Maximum
length
**
(m)
Tube
or pipe
size
***
(DN)
Maximum
capacity
(kg/h)
Maximum
developed
length
†
(m)
40
68
3
40
68
6.1
50
113
3
50
100
9.2
Description
Nominal hose, tubing
or pipe size
Steam loss
Insulation thickness
Noninsulated
Insulated
DN
kg/h/m
kg/h/m
mm
Hose
40
0.220
N/A
N/A
50
0.300
N/A
N/A
Tubing
40
0.164
0.030
50
50
0.210
0.037
50
Pipe
40
0.330
0.030
50
50
0.380
0.037
50
VM99-C-0302-M-0302.pdf 18