12
HUMIDI-TECH
®
DISPERSION
Installing Space Distribution Units
(SDUs)
Provide at least 150 mm clearance on each side of
the SDU.
Field wiring is required to connect the SDU fan and
airflow proving switch terminals to the respective
HUMIDI-TECH electrical panel terminals. Refer to
the external connections diagram in the package
shipped with your unit.
A HUMIDI-TECH with an SDU is a class-one-rated
assembly. It has been tested and is in compliance
with the requirements to be mounted in areas
accessible to the general public.
When performing HUMIDI-TECH
maintenance
If the SDU-E or SDU-I is installed immediately
above the HUMIDI-TECH, disconnect both hose
clamps on the steam hose, grip the hose and rotate
it to break it loose from the tubing, and then slide
the hose up onto the SDU steam tube until sufficient
clearance is provided to move the tank.
SDU-E mechanical detail
DC-1078
57 mm
DN40 or DN50
steam inlet
614 mm
Steam
outlet
472 mm
276 mm
57 mm
Front view
Side view
DN40 steam inlet
472 mm
614 mm
Air intake
grille
Humidified air
discharge grille
276 mm
SDU-I mechanical detail
Front view
Side view
DC-1076
409 mm
DN40 or DN50
steam inlet
409 mm
Note: Maximum ambient RH must not exceed
45% for the SDU-I to operate properly.