07-00283 C     12-02 Copyright 1999, Dri-Eaz Products, Inc.

 

11 

TROUBLESHOOTING QUICK REFERENCE SUMMARY 

 

WARNING: All service procedures below are to be executed with power off  

–  i.e. unplugged! 

 

PROBLEM 

SOLUTION 

POWER ON 

– NO INDICATOR LIGHTS 

 

  Check that the unit is plugged in, and that the circuit is 

supplying power to the unit. 

  Check the two "Main" fuses (see Fuse Diagram).  

DRITEC 325 ONLY: 

"BLOWER ON" OR "HEATER ON"  
LIGHT IS OFF 

 

  Check fuses. Do not replace until determining cause of 

the fault. Always use the same type and rating fuses. 

  Check for blocked reactivation air stream. 

  Check for correct line voltage (± 10%). 

  Check heating elements and blower motor. 

REACTIVATION OUTLET 
TEMPERATURE TOO LOW 

– 

SHOULD BE ABOUT 30°F (17°C) 
ABOVE THE TEMPERATURE OF THE ROOM

 

  Check for source of increased moisture in the space 

being processed, such as ducting leaks, open doors or 
windows, etc. 

  Check for failed heater elements. 

  Check that the blower wheel is turning freely. 

POOR DEHUMIDIFYING 
PERFORMANCE 

– UNIT IS RUNNING 

 

  Check for blocked air filter, blocked air inlet, or blocked 

air outlet(s). 

  Check for increased humidity loads. Check the process 

space for open doors, leaks in the ductwork etc. 

  Check for low temperature at the reactivation outlet. 

  Check the heating elements. 

  Check for rotation of rotor. 

ROTOR HAS STOPPED 

 

  Check fuses. Do not replace until determining cause of 

the fault. Always use the same type and rating fuses. 

  Check drive belt and motor. 

  Check for worn seals. 

 

 

Dri-Eaz Service Department (360) 757-7776 

 

 

Содержание DRITEC 150

Страница 1: ...s manual includes important safety warnings and operating information Please read before using the dehumidifier and save for future reference PURCHASE DATE _________________________ SERIAL NO ________...

Страница 2: ...Proper dehumidification helps to speed the drying of wet carpet cushion floors walls contents and structural materials It also prevents mold and mildew growth caused by moist or humid conditions The...

Страница 3: ...ard Always secure the unit to prevent sliding when transport ing in a vehicle which could cause injury to vehicle occu pants or damage to the vehicle or unit PRINCIPLES OF OPERATION DriTec Desiccant D...

Страница 4: ...move little additional water At this point many materials in the room such as carpets and wall surfaces may feel dry but moisture may remain in structural materials Ceilings walls and structural floor...

Страница 5: ...mum efficiency That is all doors windows and other openings to the outside should be closed tightly with the exception of an opening for the reactivation outlet wet air duct Locating the Dehumidifier...

Страница 6: ...o the unit If enough condensed water collects and blocks the air flow the unit can shut itself down Ducting Length The amount of air flow through the react and process ducting is dependent upon its di...

Страница 7: ...the air seals for any signs of abrasion or cuts Be sure the outer surface of the seals are smooth If the seals must be replaced please contact the Dri Eaz Service Department Check the Rotor 1 With the...

Страница 8: ...ircuit or for any mechanical problem that might keep it from turning freely 5 Restarting the unit Do not attempt to restart the unit until it is determined what caused the fault condition and correcti...

Страница 9: ...eals should be smooth If the seals must be replaced please contact the factory for in structions Checking the Heater Elements 1 The PTC heating elements are located behind the front panel just below t...

Страница 10: ...me 250 CFM 110 CFM Reactivation Air Volume 75 CFM 30 CFM Air Filter Cleanable Foam Cleanable Foam Max Reactivation Heater 4 5 kW 230 VAC 3 0 kW 115 VAC Max FLA 24 Amps 12 Amps Max Operating Temp For D...

Страница 11: ...ACTIVATION OUTLET TEMPERATURE TOO LOW SHOULD BE ABOUT 30 F 17 C ABOVE THE TEMPERATURE OF THE ROOM Check for source of increased moisture in the space being processed such as ducting leaks open doors o...

Отзывы: