Mooney Controls
Dresser, Inc.
Salt Lake City, Utah
Slam Shut Sense
Under Pressure
Trip Control
Valve
Over Pressure
Trip Control
Valve
Filter
Type 30
Restrictor
Type 24
Pilot Sense
Pilot Series 20
Loading
Outlet
Inlet
Outlet
Vent Valve
Latched
Vent
Actuator
Flowgrid Regulator &
Integral Slam Shut Valve
Flapper Valve
(Open Position )
Center Port
Flowgrid Slam Shut | 3
Figure 4 – Slam Shut Nameplate
Figure 5 – Actuator & Latch Mechanism Open
Nameplate Information
Flowgrid Nameplate information, see the Flowgrid IOM.
5. The Slam Shut Nameplate location.
6. The Flowgrid Nameplate location.
7. The flow direction is marked on the spring case or cover
(“INLET” and/or a flow arrow). Proper alignment assures
that the diaphragm guide on the Spring Case is aligned
toward outlet side of the regulator.
8. The % Capacity tag indicates the capacity of the throttle
plate (100%, 75%, 50%, & 35%) in the valve.
NOTE: On all 2” standard port valves the throttle plate
itself is stamped. This tag is not installed on stand
alone Slam Shuts.
9. Over pressure spring range nameplate. The factory
marks the nameplate to indicate which spring is installed
during manufacture. If the spring is changed make sure
to note it on the nameplate.
10. Under pressure spring range nameplate. The factory
marks the nameplate to indicate which spring is installed
during manufacture. If the spring is changed make sure
to note it on the nameplate.
Item
Definition
NITRILE
The Slam Shut has all nitrile soft
goods.
VITON
The Slam Shut has nitrile static
seals and viton dynamic seals and
diaphragms.
MAX INLET
Maximum inlet pressure psig/bar
MIN DIFF
Minimum difference in inlet and
downstream pressure required for
the Slam Shut to operate.
OP. TEMP.
Operation Temperature range
Principal of Operation
During normal operation the latch mechanism holds the
closure element (flapper) open as shown in Figure 5. The
sense or downstream pressure is monitored by the high and/
or low trip controller diaphragms. The controller diaphragms
convert the sense pressure into a force proportional to the
pressure. The force produced by the controller diaphragm is
counter balanced by the set point adjustment spring located
in the spring case. The adjusting screw is used to vary the
spring force and control the over pressure set point or the
under pressure set point.