Flowgrid Slam Shut | 9
6. Working Monitor with Slam Shut
1st Stage Regulator and Slam Shut Details
1st Stage Regulator and Slam Shut
1. Pilot #1, controls the Interstage pressure
2. Slam Shut inlet port tap on the valve body plugged (hidden).
3. Type 30 Filter inlet connected to the inlet port on the Flowgrid
®
regulator.
4. Type 30 Filter outlet connected to the inlet of the Type 24 Restrictor.
5. Type 24 Restrictor mounted to the inlet port of the Series 20 Pilot #1.
6. Series 20 Pilot #1 loading port connected to the Flowgrid
®
regulator loading port.
7 Series 20 Pilot #1 outlet port connected to the inlet port on Series 20 Pilot #2.
8. Series 20 Pilot sense port connected to the Interstage.
9. Series 50 Controller sense port connected to the piping the slam shut is protecting.
10. Pilot Cartridge assembled in PRV mode (pressure reducing).
11. Series 20 Pilot #2, controls the downstream pressure if the 2nd stage regulator fails.
12. Series 20 Pilot #2 outlet port connected to the Flowgrid
®
regulator outlet port tap.
13. Series 20 Pilot #2 sense port connected to the piping downstream of the 2nd regulator.
2nd Stage Regulator
14. Series 20 Pilot #3, controls the downstream pressure.
15. Type 30 Filter inlet connected to the inlet port tap on the Flowgrid
®
regulator.
16. Type 30 Filter outlet connected to the inlet of the Type 24 Restrictor.
17. Type 24 Restrictor mounted to the inlet port of the Series 20 Pilot #3.
18. Series 20 Pilot #3 loading port connected to the Flowgrid
®
regulator loading port.
19 Series 20 Pilot #3 outlet port connected to the outlet port tap on the Flowgrid
®
regulator.
20. Series 20 Pilot #3 sense port connected to the downstream piping.
8
16
14,10
20
9
18
13
8 - 10 Straight
Pipe Diameters
6 Straight Pipe
Diameters
or 36” which-
ever is greater
15
19
17
1, 10
12
3
2
12
6
4
10, 11
7
8
9
5