Current
Nominal
– Nominal current for use with the current threshold settings
below. Settable range is 1 – 65535 IRMSl.
Current Probe Full Scale (IRMS)
– Full scale of the CT’s being used.
Settable range is 1 – 3000. (0.333mVRMS = x amps, x is the full scale).
CT Ratio Primary
– CT primary (if applicable). Settable range is 1 –
65535.
CT Ratio Secondary
– CT secondary (if applicable). Settable range is 1 –
65535.
High Threshold %
– Current high trigger limit. Settable range is 100 –
500% of the nominal current setting.
Low Threshold %
– Current low trigger limit. Settable range is 0 – 100%
of the nominal current setting.
Input Order
– Dropdown selectable. Corrects for current wiring mistakes.
Selections are: A-B-C (default), A-C-B, B-A-C, B-C-A, C-A-B, C-B-A.
Energy
Enable
– Checkbox enable/disable.
Demand Interval Min
– Settable range is 1 minute - 1440 minutes.
Demand Sub-Interval
– Settable range is 1 minute - 1440 minutes.
Demand Limit
– When exceeded the Demand LED on the front panel will
change to RED to indicate the programmed limit has been exceeded.
Journal/Snapshot
Journal Enable
– Checkbox enable/disable.
Journal Insterval Sec.
– Journal interval entered in seconds. Value
entered must be
≥
1 second.
Snapshot Enable
– Checkbox enable/disable.
Snapshot Interval Sec.
– Snapshot interval in seconds. Value entered
must be
≥
60 seconds.