27 

3 Phase, 3 probe Delta 

The figure below shows the 3 Phase, 3 probe, 2 wattmeter delta 
connection using phase channels A-B-C. The N channel is chosen as the 
reference and is connected to phase B for measurement purposes. 
Current probes are connected to measure line currents A, B and C. Note 
that the B current probe is connected to measure the B phase current 
only and is not included as part of the power computations. 
 

NOTE 

Be sure to connect the current probes with the arrow 
pointing towards the load or an erroneous power reading 
will result. 

 

 

Содержание DranXperT

Страница 1: ...Quick Reference Guide Dranetz 1000 New Durham Road Edison New Jersey 08818 Telephone 1 800 372 6832 or 732 287 3680 Fax 732 248 1834 www dranetz com...

Страница 2: ...who has received safety training on the hazards involved Qualified personnel who work on or near exposed energized electrical conductors must follow applicable safety related work practices and proced...

Страница 3: ...ado ANSI NFPA 70E 2018 de los E E U U y cualquier requisito de seguridad adicional del lugar de trabajo aplicable a su instalaci n AVERTISSEMENT Si l instrument est mal connect la mort des blessures g...

Страница 4: ...zugeh rigen Gefahren vertraut ist Qualifiziertes Personal das an bearbeiten oder herausgestellte angezogene elektrische Leiter sich n hern mu anwendbare Sicherheit bezogener Arbeit Praxis und Verfahre...

Страница 5: ...nnection of the instrument on live power lines Connections must be made to the instrument first then connect to the circuit to be monitored Wear proper personal protective equipment including safety g...

Страница 6: ...Connecting Voltage Measurement Cables 19 Connecting Current Probes 20 DranXperT USER INTERFACE 28 Home Information Page 28 Instrument Settings 29 Real Time Measurements 36 Downloading and Managing Dat...

Страница 7: ...er and energy studies and basic power quality surveys DranXperT can be used in portable temporary remote or fixed installed applications All user interactions with DranXperT are performed using a web...

Страница 8: ...the battery fully before using the instrument The instrument will fully charge its internal battery in approximately 15 hours The instrument will always operate on the AC power source when available...

Страница 9: ...una fuente de voltaje de ca que no sea la entrada de voltaje nominal indicada en la placa de identificaci n de la unidad puede causar da os a la unidad MISE EN Mettez toujours l interrupteur dans la...

Страница 10: ...to the DC input of the instrument 2 Connect the appropriate power cord for the voltage rating of the instrument to the AC adapter battery charger 3 Plug the AC adapter into an AC power source 4 Press...

Страница 11: ...10 Controls Indicators and Connectors Top View...

Страница 12: ...D Demand Limit LED status indicator Under Demand Limit LED GREEN Over Demand Limit LED RED Energy LED status indicator Exporting producing Energy LED GREEN Importing consuming Energy LED RED Power Sou...

Страница 13: ...with an insulated BNC connector to the instrument channels A B C and N See section Connecting the Voltage and Current Connectors for circuit connection details V and I Connection LEDs color coded to i...

Страница 14: ...nection to maintain accurate measurements DC Power Input external AC adapter battery charger input Ethernet Wired Ethernet RJ45 network connector Depending on your computer an Ethernet crossover cable...

Страница 15: ...z Notes when using the default IP address If you intend to use DranXperT directly connected to a computer or on a small un routed private network it may be sufficient to use the default instrument IP...

Страница 16: ...s to be changed to be on the same network as DranXperT s default IP address This involves changing the IP address properties of your computer Please contact your IT department or Dranetz Technical Sup...

Страница 17: ...16 Step Action When finished entering the username and password click the OK button 7 The DranXperT Home Page will then be displayed Result The following screen is displayed...

Страница 18: ...de instalaci n y operaci n durante el uso de este instrumento AVERTISSEMENT Si l instrument est mal connect la mort des blessures graves ou un danger d incendie peuvent s en suivre Lisez attentivement...

Страница 19: ...m Dranetz Note that a variety of kits are available from Dranetz that include current probes Use only Dranetz voltage leads current probes and adapter cables for proper operation and safety Do not exc...

Страница 20: ...ction of all voltage measurement inputs are rated at 600 VRMS max When measuring voltages greater than 600 VRMS potential transformers PTs or other transducers must be used Contents A cable set consis...

Страница 21: ...cessary for correct power measurements where in phase voltage and current measurements are necessary Contact the Dranetz for information on availability and pricing of current probes The following saf...

Страница 22: ...EZ PAS les noyaux courants non isol s de sonde autour d un fil nonisol Des sondes de ce type sont concues pour l usage autour des fils isol s seulement L utilisation seulement a compl tement isol des...

Страница 23: ...nt and power measurement Current probes are always oriented with the arrow pointing to the load WARNING WARNING To reduce the risk of fire electric shock or physical injury it is strongly recommended...

Страница 24: ...as the reference for measurement purposes You may optionally measure the Neutral current by connecting a current probe to the Neutral conductor and to the N channel current input NOTE Be sure to conne...

Страница 25: ...utral is chosen as the reference for measurement purposes You may optionally measure the Neutral current by connecting a current probe to the Neutral conductor and to the N channel current input NOTE...

Страница 26: ...rrent probes The neutral is connected to common and is the reference for the three voltage channels Note that the Neutral current measurement is optional NOTE Be sure to connect the current probes wit...

Страница 27: ...using phase channels A B C The N channel is connected to phase B as the reference for measurement purposes Current probes are connected to measure line currents A and C NOTE Be sure to connect the cu...

Страница 28: ...s connected to phase B for measurement purposes Current probes are connected to measure line currents A B and C Note that the B current probe is connected to measure the B phase current only and is no...

Страница 29: ...wer source battery charge status IP address and current time At the bottom of the page there is a button to turn monitoring ON or OFF If monitoring is OFF click this button to turn monitoring ON and v...

Страница 30: ...instrument s settings as described below Survey Setup Select Setup Survey Setup to view change the current monitoring settings of the instrument Note that the survey setings can only be modified if m...

Страница 31: ...than the Total Trigger Cycles Total Trigger Cycles Total number of RMS points in cycles to record when exceeding the voltage or current trigger limits set below Entry range is from 0 to 600 Cycles Vo...

Страница 32: ...range is 0 100 of the nominal current setting Input Order Dropdown selectable Corrects for current wiring mistakes Selections are A B C default A C B B A C B C A C A B C B A Energy Enable Checkbox ena...

Страница 33: ...rd the settings Instrument Setup Select Setup Instrument Setup to view change the current instrument setup These are miscellaneous instrument settings such as the Ethernet settings date time etc Note...

Страница 34: ...ate and Time Note The time and date of data stored in the DranXperT database is recorded in UTC time By setting the local time zone offset below the data will appear in DranXperT and Dran View XP in t...

Страница 35: ...st You can also enter a custom setting in minutes This setting is the length of time that the data file is retained in instrument memory before it is marked for deletion from the database automaticall...

Страница 36: ...via your web browser s file download feature When prompted select Save or Save as in your web browser The file will be stored on your computer in the folder where your web browser saves downloaded fil...

Страница 37: ...Click the UPLOAD button to transfer the configuration file to the instrument 3 Update Click the UPDATE button to save the configuration information into the instrument 4 Complete When Complete is high...

Страница 38: ...age VRMS A B C RMS Current IRMS A B C True Power W A B C Apparent Power VA A B C Reactive Power VAr A B C Power Factor A B C Voltage THD A B C Current THD A B C RMS Voltage Fundamental VRMS A B C RMS...

Страница 39: ...eactive Demand VAr A B C Peak Apparent Demand VA A B C Peak Demand Fund W A B C Peak Reactive Demand Fund VAr A B C Peak Apparent Demand Fund VA A B C Downloading and Managing Data Select Data List Fi...

Страница 40: ...completed your web browser will prompt you to open or save the zip file Click Save or Save As to save the file to your web browser s Download folder name and location are browser dependant 4 Once the...

Страница 41: ...files are of the file type json 5 When the above is completed the DranXperT data is ready to be viewed by Dran View XP See the View Recorded Data section below Deleting data files from DranXperT s mem...

Страница 42: ...ent can be found on the Instrument Status page Dranetz product firmware updates and information can be found here www dranetz com technical support request software firmware updates If the firmware po...

Страница 43: ...he version displayed matches the new version installed Please contact Dranetz for any assistance Restore Factory Defaults There may come a time when you need to restore DranXperT s settings to its fac...

Страница 44: ...t Factory Restart Change Password The default username and password for DranXperT are listed above in the Connecting to DranXperT section The username cannot be changed but the password can be changed...

Страница 45: ...do one of the following to start monitoring Instrument Keypad Press and hold the Monitoring button for approximately 5 seconds until a beep is heard to turn monitoring ON The LED above the button wil...

Страница 46: ...ing button for approximately 5 seconds until a beep is heard to turn monitoring OFF The Monitor LED will turn OFF when monitoring is stopped Web Browser Select the Information Status page At the botto...

Страница 47: ...ee the Start Stop Monitoring section above Data cannot be copied to a USB drive when monitoring is ON b Insert a USB drive into the USB port c DranXperT will automatically begin copying all data files...

Страница 48: ...47 Once the data file is opened Dran View XP will display the data recorded by DranXperT You can view Time Plots Event details and more for analysis and reporting...

Страница 49: ...ach instrument External Power Supply 5V output and US 115V power cord DRANXPERT PS US External Power Supply 5V output and European Schuko 250V power cord DRANXPERT PS EU External Power Supply 5V outpu...

Страница 50: ...escription Part Number Current Probe Accessories Hinged Split Core Current Probes 600V CAT III 5A 0 4 in 10 mm window size CT H 5A 20A 0 4 in 10 mm window size CT H 20A 50A 0 4 in 10 mm window size CT...

Страница 51: ...90 VRMS to 600VRMS 0 1 90 VRMS 0 5 Connections 4 safety banana voltage inputs 3 phase voltage and 1 neutral reference Current 4 Input 0 333 VRMS full scale Connections BNC Accuracy 0 1 probe Frequency...

Страница 52: ...ry Rechargeable lithium Ion battery pack UL recognized Run time 7 hours typical Charge time 15 hours typical COMMUNICATION INTERFACES Ethernet 10 USB 2 0 Protocols Modbus Bacnet ENCLOSURE MECHANICAL M...

Страница 53: ...apply to any defects resulting from improper or inadequate maintenance buyer supplied hardware software interfacing unauthorized modification or misuse of the equipment operation outside of environmen...

Страница 54: ...itle 17 et seq No part of this publication may be reproduced transmitted transcribed stored in a retrieval system or translated into any language or computer language in any form by any means electron...

Страница 55: ...54 Page intentionally left blank...

Страница 56: ...by Dranetz 1000 New Durham Road Edison NJ 08817 USA Telephone 1 800 372 6832 or 732 287 3680 Fax 732 248 1834 Web site www dranetz com Copyright 2020 Dranetz All rights reserved P N QR DRANXPERT Rev A...

Отзывы: