30
General
Survey Name
- Enter a name (up to 48 characters) that describes your
survey. This name will be inlcuded in the name of the data file recorded.
Nominal Frequency
– Dropdown selection, either 50 Hz or 60 Hz.
Wiring Configuration
– Dropdown selections are: Single Phase, Split
Phase, Three-Phase Wye, Three-Phase Delta 2 probes, Three-Phase
Delta 3 probes.
Enable Monitor On Power Up
– Checkbox enable/disable. When
checked, if the instrument resets, such as when power is restored after
the battery has depleted, monitoring will be re-enabled upon restart if
moniting was previously ON.
Pre-trigger Cycles
– Number of pre-trigger RMS points (in cycles) to
record when exceeding the voltage or current trigger limits set below.
Must be less than the Total Trigger Cycles.
Total Trigger Cycles
– Total number of RMS points (in cycles) to record
when exceeding the voltage or current trigger limits set below. Entry
range is from 0 to 600 Cycles.
Voltage
Nominal
– Nominal voltage. Settable range is 90 – 600VRMS.
PT Ratio Primary
– PT primary (if applicable). Settable range is 1 –
65535.
PT Ratio Secondary
– PT secondary (if applicable). Settable range is 1 –
65535.
Sequence Error Enable
– Checkbox enable/disable. Enables connection
panel LED notification of a voltage sequence/connection error. The LEDs
will flash RED if enabled and a voltage sequence error exists.
High Threshold %
– Voltage high trigger limit. Settable range is 100 –
500% of the nominal voltage setting.
Low Threshold %
– Voltage low trigger limit. Settable range is 0 – 100%
of the nominal voltage setting.
Input Order
– Dropdown selectable. Corrects for voltage wiring mistakes.
Selections are: A-B-C (default), A-C-B, B-A-C, B-C-A, C-A-B, C-B-A.