Dräger Polytron 8200/8310
Technical data
12.3.2 Unalterable settings
Fault
Meaning
Fault relay / wired
in e-Box
Energized / NO
Yellow Fault LED Lights when a fault is present
Red Alarm LED
Gives single flashes when an A1 alarm
is present.
Gives double flashes when an A2 alarm
is present.
If an alarm is configured as
acknowledgeable and the alarm is
acknowledged, the LED lights.
Alarm hierarchy: A2 has a higher priority
for the LED than A1. However the A1 and
A2 relays operate independently of one
another, i.e. if A1 is acknowledgeable and
A2 is not and the gas concentration is
so high that A1 and A2 are triggered,
an acknowledgement results in the A1
relay dropping out. However the red LED
continues to give double flashes as long
as the A2 condition exists.