Factory default settings
|
en
Instructions for use
|
Dräger PointGard 2000 Series
29
15.2.3 PointGard 2200 CAT DrägerSensor
®
LC
15.2.4 PointGard 2200 CAT Remote DSIR
15.2.5 PointGard 2700 IR
Type 334
Hysteresis for A1
alarm at direction
rising
1 % LEL
0 to A1
Hysteresis for A2
alarm at direction
rising
1 % LEL
0 to A2
Calibration inter-
val [days]
180
0 to 360
Display capture
offset
0 % LEL
-5 to 4 %LEL
Display capture
low
-5 % LEL
-5 to 0 %LEL
Display capture
high
2 %LEL
0 to 4 %LEL
Full scale deflec-
tion
100 %LEL
Range is not
adjustable
Menu
Default setting
Range
A1 Alarm
2.0 % LEL
0.1 to 10 % LEL
A2 Alarm
4.0 % LEL
Hysteresis for A1
alarm at direction
rising
0.1 % LEL
0 to A1
Hysteresis for A2
alarm at direction
rising
0.1 % LEL
0 to A2
Full scale deflec-
tion
10 % LEL
5 to 10
1)
% LEL
1 to 10 % LEL
1) For firmware versions < 3.0.0
Calibration inter-
val [days]
180
0 to 360
Display capture
offset
0 % LEL
-0.5 to 0.4 % LEL
Display capture
low
-0.5 % LEL
-0.5 to 0 % LEL
Display capture
high
0.2 %LEL
0 to 0.4 % LEL
Menu
Default setting
Range
A1 Alarm
20 % LEL
1 to 100 % LEL
A2 Alarm
40 % LEL
Hysteresis for A1
alarm at direction
rising
1 % LEL
0 to A1
Hysteresis for A2
alarm at direction
rising
1 % LEL
0 to A2
Menu
Default setting
Range
Calibration inter-
val [days]
180
0 to 360
Display capture
offset
0 % LEL
-3 to 4 % LEL
Display capture
low
-3 % LEL
-3 to 0% LEL
Display capture
high
2 %LEL
0 to 4% LEL
Full scale deflec-
tion
100 %LEL
Range is not
adjustable
Menu
Default set-
ting
Range
Calibration
gas
Methane
Calibration
gas units
%LEL
Calibration
gas concen-
trations
50 %LEL
A1 Alarm
20 %LEL
0.01 to 100 Vol% at unit
%LEL = 0.3 to 100 %LEL
A2 Alarm
40 %LEL
LEL type
NIOSH
IEC / PTB / NIOSH / configu-
rable
Measured
gas
Methane
Measured
gas units
%LEL
%LEL / Vol% / PPM / %LEL /
%LIE
Full scale
deflection
100 % LEL
20 to 100 %LEL
Beam block
Off
On / Off
Beam block
current
2 mA
0 to 3.5 mA
Beam block
limit
7.5 %LEL
0 to max. 15 %LEL
1)
Calibration
interval
[days]
360
0 to 720
Response
Normal
Normal / Fast
Menu
Default setting
Range