14
Use
en
Using either the RS-485 interface or the HART protocol, you can
reprogram the following parameters:
Alarm delay
Address setup
Mode of operation
Heat mode
To change the configuration parameters the following accessories are
required:
Dräger Flame USB RS-485 Kit and corresponding manual:
The harness kit with RS-485/USB converter, used with the host
software, enables you to connect to any available PC or laptop to
reconfigure settings or perform diagnostics on all Dräger
Flame 2xx0 detectors.
Possible alarm delay settings
The flame detector is equipped with an alarm delay option. It can be
set to one of the following options:
Antiflare (A)
The antiflare mode is selected to prevent false alarms in locations
where fast flares may be present. The time delay for fire alarms in
this mode is calculated by the detector software and ranges from
2.5 to 15 seconds (usually less than 10 seconds).
or
0, 3, 5, 10, 15, 20 or 30 seconds
When an alarm threshold condition occurs, the flame detector delays
the execution of the alarm outputs by the specified period of time. The
flame detector then evaluates the condition for 3 seconds. If the alarm
threshold condition is still present, the alarm outputs are activated. If
the alarm threshold condition no longer exists, the flame detector
returns to its standby state.
The alarm delay option affects alarm relay, fault relay, and 0-20 mA
output. The status LED and outputs indicate warnings during the delay
time. When the delay time has passed, status LED and outputs
indicate the alarm.
Possible address setups
A system with up to 247 addresses can be configured.
Possible modes of operations
Function
Setting
Alarm Latch
YES: Enable alarm latching.
NO: Disable alarm latching (default).
Automatic BIT
1)
1)
not applicable for Dräger Flame 2370
YES: Perform automatic & manual BIT
(default).
NO: Perform manual BIT only.
Alarm BIT
1)
YES: Successful manual BIT activates
the alarm relay for approximately
3 seconds (default).
NO: Successful manual BIT does not
activate the alarm relay.
Auxiliary Relay
2)
2)
only available in wiring option 4 and 5
YES: Activate auxiliary relay at warning
level.
NO: Activate auxiliary relay at alarm
threshold (default).
(The auxiliary relay is latched only when the
programmable function Auxiliary Relay is
set to YES.)
Auxiliary BIT
1, 2)
YES: Successful manual BIT activates
the auxiliary relay for approximately
3 seconds (default).
NO: Successful manual BIT does not
activate the auxiliary relay
Содержание Flame 2100
Страница 2: ......
Страница 120: ...120 ru 1 1 1 5 135 Dr ger Dr ger Dr ger Dr ger Dr ger 1 2 2 2 1 A 1 2 3 4 5 6 7...
Страница 121: ...121 ru 2 2 2 2 1 Dr ger Flame 2100 0 185 0 260 2 2 2 Dr ger Flame 2350 200 0 185 0 260 4 4 4 6 CO2...
Страница 122: ...122 ru 2 2 3 Dr ger Flame 2370 20 0 185 0 260 2 5 3 0 H2O 2 2 4 3 5 C 5 8 F 5 7 2 136 0 20 3 4 2 133 Modbus RS 485 HART...
Страница 126: ...126 ru 3 3 1 NFPA 72 Ex 3 NFPA 72 30 12 45 18...
Страница 127: ...127 ru Dr ger Flame 2350 2370 45 3 2 3 344...
Страница 130: ...130 ru A 2 5 15 10 0 3 5 10 15 20 30 0 20 247 BIT 1 BIT BIT BIT 1 BIT 3 BIT 2 YES...
Страница 134: ...134 ru 4 0 20 0 Dr ger 4 0 20 0 24 Dr ger 4 0 20 2 BIT Dr ger 0 20 20 Dr ger...
Страница 135: ...135 ru 5 5 1 Dr ger 5 2 1 2 3 5 3 1 2 3 3 9 131 3 Dr ger 6 5 2 135 5 3 135 6 1 1 Dr ger Dr ger...
Страница 144: ......
Страница 145: ......