background image

9

Dräger Flame 3000

Use

3.1 

Prerequisites for installation

When selecting a mounting position for the Dräger Flame 3000 

observe the following:

• 

Ensure that the Dräger Flame 3000 has an unobstructed view of 

the areas to be protected.

• 

Ensure that the mounting position is free from vibration or 

movement.

• 

Ensure that the mounting position has sufficient support for the 

Dräger Flame 3000 and allows for horizontal adjustment.

• 

Ensure that the Dräger Flame 3000 is protected from sources of 

impact damage and from being knocked out of alignment.

• 

Install the Dräger Flame 3000 as far away as possible from local 

sources of possible electrical interference, such as X-rays, RF 

(radio frequency) interference or electrostatic discharge.

• 

Ensure  that  the  area  under  observation  has  sufficient  detector 

coverage for all possible hazards (multiple detectors may be 

required) taking into account any obstructions and congestion.

• 

Minimize the exposure of the enclosure front cover window to 

contaminants such as oil, water (deluge water, rain and sea spray), 

snow, and ice. Where the Dräger Flame 3000 is to be mounted at 

a low level avoid contamination from equipment situated above 

the mounting position.

• 

If dense smoke is expected to accumulate at the onset of the fire, 

the Dräger Flame 3000 should be mounted 1 – 2 m below the 

ceiling level where possible.

• 

Ensure there is maintenance access to the Dräger Flame 3000 

(e.g. direct, ladder or scaffold access).

• 

Ensure that mounting supports are compatible with the Dräger 

Flame 3000 mounting brackets.

• 

Ensure that the Dräger Flame 3000 does not have a direct view 

of any sources of flame used during normal operations, such as 

flare stacks.

• 

Ensure that the Dräger Flame 3000 is positioned so that it is not 

directly facing the sun.

All of these issues are crucial to a successful installation. They 

should be observed during the detailed design, construction and 

commissioning phases of the installation of a fire detection system.

3.1.1 

Detector coverage

Software analysis of the actual detector field of view may be required 

to ensure adequate coverage of the hazards. This analysis can also be 

used to optimize the number of detectors and the loop configuration.

3.1.2 

Power and cable requirements

The Dräger Flame 3000 requires a supply voltage of 18 – 30 V at the 

input terminals.

The installation location and local regulations and standards determine 

the cable specification.

The Dräger Flame 3000 contains further details of the power and 

cable selection requirements. Contact Dräger for details.

Use

Содержание 420 94 60

Страница 1: ...lame 3000 Visual Flame Detector Instructions for Use WARNING Strictly follow the Instructions for Use The user must fully understand and strictly observe the instructions Use the product only for the...

Страница 2: ......

Страница 3: ...xplanation of type identifying marking and symbols 8 3 Use 9 3 1 Prerequisites for installation 9 3 2 Installation 10 3 3 Commissioning and functional testing 14 4 Troubleshooting 15 5 Maintenance 16...

Страница 4: ...activities Use only genuine Dr ger spare parts and accessories or the proper functioning of the product may be impaired Do not use a faulty or incomplete product and do not modify the product Notify D...

Страница 5: ...e following main components Front enclosure cover including the window Detector assembly Enclosure body Terminal connections Rear enclosure cover Mounting bracket The Dr ger Flame 3000 is supplied pre...

Страница 6: ...oes not have a traditional cone of vision like infrared flame detectors Its field of view is a rectangular pyramidal shape and represents a radial projection of the rectangular sensing element within...

Страница 7: ...r use of the device in gas vapour air mixtures of combustible gases and vapours under atmospheric conditions The explosion protection is not valid for use in oxygen enriched atmospheres WARNING Do not...

Страница 8: ...r ger Flame 3000 is insensitive to arc welding arc welding should not take place within 1 m of the flame detector 2 5 Approvals ATEX Certificate number FM07ATEX 0033 II 2 G Ex db IIC T4 IECEx Certific...

Страница 9: ...the mounting position If dense smoke is expected to accumulate at the onset of the fire the Dr ger Flame 3000 should be mounted 1 2 m below the ceiling level where possible Ensure there is maintenance...

Страница 10: ...should only be installed after these tests are complete Do not drop or knock the enclosure as this may damage the detector assembly Only appropriately trained service personnel may open the enclosure...

Страница 11: ...he mounting location using 8 mm fastenings 2 Orientate the Dr ger Flame 3000 so that it provides the desired coverage and securely fix in place Ensure that it is orientated so that the status LED and...

Страница 12: ...10 B 11 B 12 Alarm 24 Vdc 0 Vdc To fire panel To fire panel 4 20mA source 0 Vdc 24 Vdc 0 Vdc End of line resistor Alarm Alarm relay normally open Fault relay normally closed Event Output Power detecto...

Страница 13: ...sure that the O ring is beneath the cover and that the set screw will not interfere with or be screwed into the threads of the flame path or the O ring Secure the rear enclosure cover in place with th...

Страница 14: ...d system initialization that takes approximately five seconds 2 Test the Dr ger Flame 3000 using a flame simulator refer to the flame simulator instructions for details Dr ger recommend the Dr ger FS...

Страница 15: ...pair Any attempt to dismantle remove or repair the detector assembly by persons who are not appropriately trained service personnel will invalidate the warranty of the Dr ger Flame 3000 When investiga...

Страница 16: ...sks be completed every six months The actual level of maintenance required is dependant on the operating environment and the likelihood of damage or the rate of contamination from oil etc It is advisa...

Страница 17: ...ive from August 2005 and apply to this device Common household appliances can be disposed of using special collecting and recycling facilities However as this device has not been registered for househ...

Страница 18: ...mm 8 7 in 3 9 in Cable entries M20 M25 1 2 or 3 4 NPT single entries Terminal wire size 2 5 mm2 14 AWG Ingress protection IP66 NEMA 4X 7 2 2 Mounting bracket Support fixings M8 quantity 2 Vertical ad...

Страница 19: ...m 420 94 62 Single 3 4 NPT cable entry aluminum 420 94 64 Single 1 2 NPT cable entry aluminum 420 94 76 Single M25 cable entry stainless steel 420 94 68 Single M20 cable entry stainless steel 420 94 7...

Страница 20: ...raeger Safety UK Limited Ullswater Close Blyth NE24 4RG United Kingdom Tel 44 1670 352891 Fax 44 1670 544475 www draeger com 3360572 Dr ger Safety UK Limited Edition 04 March 2019 Subject to alteratio...

Отзывы: