18
Dräger Flame 3000
7
Technical data
7.1
Electrical specification
7.1.1
Power supply
Supply
voltage:
18 – 30 Vdc (24 Vdc
nominal) including ripple
Supply ripple:
1 Vpk-pk
Power consumption:
6 W
Shutdown voltage
(low supply):
< 17 Vdc
7.2
Mechanical specification
7.2.1
Enclosure
Enclosure material:
Aluminum alloy grade HE30
or stainless steel 316
Finish:
Epoxy coated finish;
Dräger
blue
Weight:
Aluminum; 2.5 kg (5.5 lb)
stainless steel;
5.5
kg
(12.1
lb)
Dimensions:
220 mm × 100 mm
(8.7 in. × 3.9 in)
Cable
entries:
M20, M25, 1/2 " or 3/4 "NPT
(single
entries)
Terminal wire size:
2.5 mm
2
(14 AWG)
Ingress protection:
IP66 (NEMA 4X)
7.2.2
Mounting bracket
Support fixings:
M8 (quantity 2)
Vertical adjustment:
0 – 45 degrees
Horizontal adjustment:
± 45 degrees
7.3
Environmental specification
Operation ambient temperature:
- 60 to + 85 °C
(-76 to + 185 °F)
Storage ambient temperature:
- 60 to + 85 °C
(-76 to + 185 °F)
Relative humidity:
0 – 90 % (non-condensing)
7.4
Operating specification
Detector range (depth of field):
0 – 60 m (0 – 200 ft)
Horizontal field of view:
120 degrees
Vertical field of view:
80 degrees
Detector response time:
10 – 30 seconds
Power on reset delay:
5 seconds
Technical Data
Содержание 420 94 60
Страница 2: ......