PRODUCT DESCRIPTION

The DRX/DRY controller controls manually the speed of single phase (230 VAC / 50 - 
60 Hz) voltage controllable motors / fans from high to low (DRX) or from low to high 
output (DRY). It is suitable for DIN rail mounting (DIN EN 50022). Multiple fans can 
be connected as long as the current limit is not exceeded. 

ARTICLE CODES

Code

Regulation 

Max. rated current

Max. load L1

Fuse 5*20mm

DRY-1-15-AT

min. to max.

1,5 A

0,5 A

3,15 A

DRX-1-15-AT

max. to min.

1,5 A

0,5 A

3,15 A

DRY-1-25-AT

min. to max.

2,5 A

0,5 A

5,0 A

DRX-1-25-AT

max. to min.

2,5 A

0,5 A

5,0 A

INTENDED AREA OF USE

 

Speed control of motors / fans in ventilation systems

 

For indoor use only

TECHNICAL DATA

 

Supply: 230 VAC ±10 % / 50 - 60 Hz 

 

Unregulated output load (L1): 230 VAC / max. 0,5 A

 

Regulated output to motor / fan, U:

 

max. load: 1,5 for DRX / DRY-1-15-AT

 

max. load: 2,5 for DRX/DRY-1-25-AT

 

Speed control:

 

DRX – from maximum to minimum

 

DRY – from minimum to maximum

 

Minimum speed adjustment by trimmer: 60—230 VAC

 

Green operating LED indication: on / off

 

Enclosure: 

 

DIN rail mounting (DIN EN 50022)

 

ABS/PC, grey (RAL 7035)

 

Protection standard: IP30 (according to EN 60529)

 

Operating ambient conditions:

 

temperature: 0—40 °C

 

rel. humidity: < 80 % rH (non-condensing)

 

Storage temperature: -14—50 °C

STANDARDS

 

Low Voltage Directive 2006/95/EC 

 

EMC Directive 2004/108/EC: EN 61326 

 

WEEE Directive 2012/19/EU

 

DIN rail EN 60715:2001

 

RoHs Directive 2011/65/EU

DR

ELECTRONIC FAN SPEED 
CONTROLLER, DIN RAIL MOUNTING

Содержание DRY-1-15-AT

Страница 1: ...Mounting and operating instructions DR ELECTRONIC FAN SPEED CONTROLLER DIN RAIL MOUNTING...

Страница 2: ...ED AREA OF USE 4 TECHNICAL DATA 4 STANDARDS 4 OPERATIONAL DIAGRAM 5 WIRING AND CONNECTIONS 5 MOUNTING OPERATING INSTRUCTIONS IN STEPS 5 VERIFICATION OF THE INSTALLATION INSTRUCTIONS 6 TRANSPORT AND ST...

Страница 3: ...condensation spots All installations shall comply with the local health and safety regulations and local electrical codes This product can only be installed by an engineer or a technician who has an e...

Страница 4: ...F USE Speed control of motors fans in ventilation systems For indoor use only TECHNICAL DATA Supply 230 VAC 10 50 60 Hz Unregulated output load L1 230 VAC max 0 5 A Regulated output to motor fan U max...

Страница 5: ...the DR speed controller read carefully Safety and Precautions Then proceed with the following mounting steps 1 Switch off the power supply 2 Mount the controller on a standard 35 mm DIN rail Pull the...

Страница 6: ...d output 230 VAC max 2 A 4 Switch on the power supply 5 Set the required output voltage with the help of the potentiometer on the front cover Adjust the minimum speed with the trimmer if necessary The...

Страница 7: ...nsibilities The manufacturer bears no responsibility for any misprints or mistakes in this data MAINTENANCE In normal conditions this product is maintenance free If soiled clean with a dry or dampish...

Отзывы: