DPS Telecom Net Dog 82 IP Скачать руководство пользователя страница 4

D-PC-295-10A-0V
May 5, 2000

4

OG113939.001

Software Configuration 

Local Connection

Connect a PC running terminal emulation software to

COM1 on back of the Net Dog (Fig. 7). Set your serial
port to match the data rate and word format currently
defined for the Net Dog’s COM1 (factory default is
9600, n, 8, 1). Connect to the Net Dog and enter
‘DPSCFG’ to activate the configuration menu.

Remote Connection (Dial Up)

Set up a PC running TTY terminal emulation soft-

ware to dial the Net Dog’s modem. When a connection
is established (sometimes accompanied by receipt of a
hex byte), enter ‘DPSCFG’ to activate the configuration
menu.

LAN Connection

In order to utilize the 10BaseT port on the Net Dog,

it must first be pre-provisioned using a remote terminal
(either dial up through the modem or directly connected
to Com 1). The LAN minimum configuration requires
setting the unit address (IP) and the subnet mask. Use of
a WAN requires that the default gateway be set.

Edit Section

Note: Menu Selection Hot Keys - The letter before a
parentheses right bracket ) or enclosed in parentheses ( )
is a hot key. When you type the hot key, you are taken to
that submenu. Most menus are two layers deep. Pressing
the <Esc> key brings you back to the previous level.
From the bottom level, pressing <Esc> twice returns to
the top menu. 

1. Edit the System Information

Perform the following steps to configure your Net

Dog. If you change a field, the change is made when
you press <Enter>.

Table A - System Submenu Fields

Fig. 8 - To begin configuration, select E)dit from the

main menu, then s(Y)stem from the E)dit submenu.

Field

Description

Name

Trap

Community Name for SNMP TRAPS 

User designated name for this Net Dog

Physical location of Net Dog

Person responsible for this Net Dog

Community Name for SNMP requests

Community Name for SNMP SET requests

Set

Get

Contact

Location

Fig. 9 - to change the value of the Name field, select

N)ame and type in the desired information.

Fig. 10 - To edit the Ethernet port parameters,

select E)Port from the P)orts submenu.

a.

Select E)dit from the main menu.

b. Select s(Y)stem from the Edit submenu. The current

system field values will be displayed. The prompt
line at the bottom of the screen lists the hot keys for
each field. (Fig. 8) The field meanings are given in
Table A. 

c.  Select the field you want and make the changes.

Figure 9 shows an example of changing the Name
field.

d. Press 

<Enter>.

e.  When you finish changing fields, press <Esc>.

2. Edit the Ethernet Port Parameters 

a.  Select P)orts from the System submenu.
b. Select E)Port from the Ports submenu. The current

E)port field values will be displayed. The prompt
line at the bottom of the screen lists the hot keys for
each field. (See Fig. 10)

Содержание Net Dog 82 IP

Страница 1: ...ains secure through power outages in non volatile RAM Status LEDs on the Net Dog give you a quick glance indication of problems on site Some of the mentioned applications require external sensors Net Dog is easy to install with connectors for all ports and captive screw lug terminals for alarm and control wiring Net Dog mounts on any vertical flat surface or you can just set it on top of your desk...

Страница 2: ... TTL alarm source by moving jumpers on the PC board The alarm inputs are set by factory default for dry contact alarm sources jumpers A C See Fig 3 for a schematic representation of the input configurations A To change an input for TTL remove the six screws on the sides of the case and lift off the cover B Locate the jumper area in the bottom right area of the circuit board Refer to Fig 5 to deter...

Страница 3: ...device and configuration port Female DB9 1 2 3 1 2 3 1 2 3 1 2 3 1 2 3 1 2 3 1 2 3 1 2 3 1 2 3 4 5 1 2 3 4 5 1 2 3 4 5 1 2 3 4 5 1 2 3 4 5 1 2 3 4 5 1 2 3 4 5 1 2 3 4 5 J10 J11 J26 J27 J28 J29 J30 J31 J5 J12 J13 J14 J24 J25 J22 J23 E F A B C D A B C D Alarm 1 2 3 4 5 6 7 8 E F Fig 4 Each alarm input has four configuration options AL 1A AL 1B Vcc TTL Internally Biased jumpers B D F AL 1A AL 1B Cont...

Страница 4: ...bottom level pressing Esc twice returns to the top menu 1 Edit the System Information Perform the following steps to configure your Net Dog If you change a field the change is made when you press Enter Table A System Submenu Fields Fig 8 To begin configuration select E dit from the main menu then s Y stem from the E dit submenu Field Description Name Trap Community Name for SNMP TRAPS User designa...

Страница 5: ...the field you want to change and make the desired changes Fig 11 shows an example of changing the entries for the Pager 3 field c Press Enter d When you have changed all the fields that need changing press the escape key Esc to return to the System submenu Field Description Baud Wfmt Port data rate 300 1200 4800 2400 9600 The default baud is 9600 Port word format default designation is 8 N 1 Data ...

Страница 6: ...ed changes Fig 14 shows an example of changing the entries for the Description field for point 1 c Press Enter d When you have changed all the fields that need changing press the escape key Esc twice to return to the System menu Fig 12 To edit the pager parameters select Pa G er from the E dit submenu Fig 13 To edit the Alarm Point Settings select E dit then the A larms submenu Field Description I...

Страница 7: ... PINGs before a FAIL is declared Likewise the CYCLE time should be set to several times the TRY time Table G Ping Information Submenu Fields Table H Timer Settings Fig 15 To edit the ping information select E dit then the pi N g submenu Field Description ID Fixed number designating the line number in the list of devices to be pinged Description Description of the device to be pinged IP Address Add...

Страница 8: ...atus of the first 16 pinged devices will be displayed Fig 20 Press Tab to view the next 16 devices c You can now select another monitor function or press Esc to return to the main menu T 8 sec C 1 min Note default times shown F 5 min C C C C Fig 17 When a target fails to respond to a ping within the fail time period a fault is declared Fig 18 To make changes effective select N Vram then W rite fro...

Страница 9: ...22 shows an example of pinging address ID 1 Note 1 32 are shortcuts for defined IP entries or any full IP address For example 3 3rd address in IP address table See Fig 15 3 The device will be pinged repeatedly and the result of each ping will be displayed on the screen see Fig 23 OK device responding NOK error code device not responding See Table K for error codes 4 Press any key to stop pinging 5...

Страница 10: ... device SNMP managers Net Dog reports to your SNMP manager will appear on screen as described in the docu mentation for your SNMP manager Alphanumeric Pager Descriptions Clear Channel Connection A clear channel connection allows you to remotely access the craft port of a device that is connected to the Net Dog s COM1 port via Ethernet Proceed as follows 1 Connect a Telnet client to TCP port 2002 a...

Страница 11: ... not simulate alarms by taking critical equipment off line open or temporarily short the alarm input to simulate a failure Do not operate control points if critical equipment will be affected disconnect the control point wires and use a con tinuity meter to verify operation then reconnect the wires ...

Страница 12: ... regarding this procedure Options and Model Numbers D PC 295 10A 01 Net Dog 82 IP 120 VAC D PC 295 10A 02 Net Dog 82 IP 24 VDC D PC 295 10A 04 Net Dog 82 IP 48 VDC Shipping List Download cable D PR 045 10A 02 Power cable transformer D PR 107 10A 00 Operation guide OG113939 001 Mib trap file disk D SW 790 10A 00 Ethernet cable 8ft RJ45 to RJ45 D PR 923 10A 08 DPM mounting kit 1 005 0001 00 Mounting...

Отзывы: