37
Alarms
11.7
Discrete alarms are configured from the
Provisioning
>
Alarms
menu. Descriptions for the alarm points, polarity
(normal or reversed) and notification type(s) are defined from this menu. You also have the option to use
Basic
or
Advanced
configuration methods, explained in this section.
The Provisioning > Alarms menu
Basic Alarm Configuration
ID
Alarm ID number.
Description
User-definable description for the discrete alarm point.
Rev (Reverse)
Reverse: Check this box to reverse the polarity of the alarm point. Leaving this option
un-checked means a normally open contact closure is an alarm. When polarity is
reversed, a normally closed alarm point is clear when closed.
Notification Devices
Check which notification device(s), 1 through 8, you want to send alarm notifications
for that alarm point.
Advanced Alarm Configuration (Advanced>>)
On Set
User-definable description (condition) that will appear for the discrete alarm input on
Set. Example: "Alarm".
On Clear
User-definable description (condition) that will appear for the discrete alarm input on
Clear: "Example: "Alarm Cleared".
Qual. Time (Qualification
Time)
The length of time that must pass, without interruption, in order for the condition to be
considered an Alarm or a Clear.
Qual. Type (Qualification
Type)
Allows you to choose whether you want to apply the Qualification Time to the alarm
Set, Clear, or Both.
Содержание D-PK-TDFG2
Страница 5: ...SNMP FAQs 17 2 102 Technical Support 18 103 End User License Agreement 19 106...
Страница 6: ......
Страница 15: ...9 Temp Defender G2 Front Panel 6 TempDefender G2 Front Panel...
Страница 23: ...17 instructions on setting up your LAN connection...
Страница 59: ...53 11 12 2 Modbus Registers Provisioning Modbus Registers...
Страница 65: ...59 Welcome screen on a mobile...
Страница 110: ...104...
Страница 111: ...105...