59
54
Battery #6 High Voltage: Warning
55
Battery #6 High Voltage: Alarm
56
Battery #6 High Voltage: Lock-Out
58-64
Undefined
Display
Point
Description
Display 36
1-16
Battery #6 Current (A)
17-32
Battery #6 Max Current (A)
33-48
Battery #6 State of Charge (%)
49-64
Battery #6 Voltage (VDC)
Display
Point
Description
Display 37
1-16
Battery #6 Remaining Capacity (Ahr)
17-32
Battery #6 Average Cell Temperature
(°C/ °F)
33-48
Battery #6 Nominal Float Voltage (VDC)
49-64
Battery #6 Estimated Runtime (minutes)
Display
Point
Description
Display 38
1-16
Battery #6 Design Max Capacity (Ahr)
17-32
Battery #6 State of Health (%)
33-48
Battery #6 Number of Complete Discharge Cycles
49-64
Battery #6 Usable Capacity (Ahr)
Display
Point
Description
Display 39
1-64
Battery #7 Serial Number
Display
Point
Description
Display 40
1-8
Battery #7 Software Version
9-16
Battery #7 Software Revision
17-24
Battery #7 Hardware Revision
25-32
Battery #7 Type ID
33-40
Battery #7 Type Switch Setting
41-48
Battery #7 Firmwre/Hardware Match
49-64
Undefined
Display
Point
Description
Display 41
1
Undefined
2
Battery #7 Not Detected
3
Battery #7 Sent to Sleep
4-32
Undefine7
33
Battery #7 Operation Mode: Initializing
34
Battery #7 Operation Mode: Wake-Up
35
Battery #7 Operation Mode: Validating
36
Battery #7 Operation Mode: Post
37
Battery #7 Operation Mode: Normal
38
Battery #7 Operation Mode: Lock-Out
39
Battery #7 In Lock-Out
40
Battery #7 Charge Mode: Initializing
41
Battery #7 Charge Mode: Float
42
Battery #7 Charge Mode: Charge
43
Battery #7 Charge Mode: Discharge
44
Battery #7 Charge Mode: Charge
45
Battery #7 Current: Warning
46
Battery #7 Current: Alarm
47
Battery #7 Current: Lock-Out
Содержание D-PK-NGBSM