18
Tbl. 3.1 -
Net Guardian Expansion LED indications.
Operation • Front Panel Functions
Operation
Chapter 3
3.1
Front Panel Functions
Fig. 3.1 –
The Front panel displays alarm and communication status.
Label Descriptions
1.
ACK button. The ACK button will acknowledge any new alarms (change of state (COS) alarms). It
will also cause the shelf address (determined by the back panel DIP switch) to be displayed by
LEDs 1-3 when it is held down.
2.
Front panel LEDs. See table below for LED indications.
LED
STATUS
DESCRIPTION
CFG
Flashing Red
Flashing Green
Invalid Shelf Address, check back panel DIP switch setting.
Shelf Address set correctly.
LNK
Solid Green
Flashing Green/Red
Data Transmit/Receive on primary RS232 port (DX IN).
PRI
1
2
SEC
Flashing Green/Red
Data Transmit/Receive on secondary RS232 port (DX OUT).
Alarms
1-8
Green = Banks
Red = Points
A green flash indicates the point bank number (1-6). A point
bank is comprised of 8 alarm points.
A red flash after the green point bank number flash indi-
cates which of the 8 alarms in that point bank are in an
alarmed state (see table below).
Note
: The Expansion alarm points are also displayed on the Net
Guardian’s LCD.
Note:
The silk screen designations “DX IN” and DX OUT” do not indicate communication direction.
Point Bank
Alarm Points
1
2
3
1-8
9-16
17-24
4
5
6
24-32
32-40
41-48
Содержание D-PC-293-10A