13
Installation • Software Provisioning
2.4.2 Provisioning the Expansion Alarm Points
Now that the Net Guardian is configured for the correct number of expansions connected to it, the 48 discrete
alarm points on each expansion can be provisioned with a description, polarity, pager IDs, and other options.
1.
From the E)dit menu, select A)larms and then E)xpansions to edit the Expansion alarm points.
2.
Each Net Guardian Expansion reports it’s alarms on a separate display. Display 12 corresponds to the alarm
points in Expansion shelf 1, display 14 corresponds to points in Expansion shelf 2, and display 16 corresponds
to points in Expansion shelf 3 (see section 3.2 for display mapping details). Enter display 12 to edit the first
Expansion’s points. A list of the first 16 alarm points will be shown.
3.
Enter an Alarm ID number to edit it’s information.
4.
From the menu that appears, select D)escription to enter a description of the alarm point (up to 23 Characters).
5.
Select po(L)arity to toggle the condition required to trigger an alarm. When the polarity is set to “Nrm,” the
alarm is wired as a normally open contact which must be closed to trigger an alarm. When the polarity is set to
“Rvs,” the alarm is wired as a normally closed contact which must be opened to trigger an alarm.
6.
Select T)rap to toggle (Yes/No) sending an SNMP Trap when that alarm occurs.
7.
Select P)ri PAger and S)ec. Pager to enter the pager ID for the primary pager and secondary pager. Refer to
the pa(G)ers section to determine which pager IDs correspond to which device/pager. (Other pager options
include e-mail notification of an alarm, or sending Traps to multiple SNMP managers.)
8.
Repeats the steps above until all 48 alarm points for each expansion are provisioned.
Fig. 2.4.2 –
Provision the Expansion points from the E)dit, A)larms, E)xpansions menu.
s(Y)stem L)ogin P)orts pa(G)ers A)larms R)elays
a(N)alogs p(I)ng info T)imers D)ate/time n(V)ram (ESC) ? A
B)ase E)xpansions (ESC) ? E
Active Displays : 12, 14, 16
Display Number : 12
SNMP .Pager.
ID
Description
Pol Trap Pri Sec
1
DOOR ALARM
Nrm
Y
1
2
2
COMMERCIAL POWER OUT
Rvs
Y
1
2
3
UPS GNRTR RUNNING
Nrm
Y
1
4
4
RECTIFIER 1
Rvs
N
2
3
5
RECTIFIER 2
Rvs
Y
3
4
6
ICY CONDITION
Nrm
N
5
1
7
GE2 DE-ICER 1 ON
Nrm
Y
4
6
8
GE2 DE-ICER 2 ON
Nrm
Y
4
6
9
GE2 DE-ICER 3 ON
Nrm
Y
4
6
10
GE2 DE-ICER 4 ON
Nrm
Y
4
6
11
Nrm
N
0
0
12
Nrm
N
0
0
13
Nrm
N
0
0
14
Nrm
N
0
0
15
Nrm
N
0
0
16
Nrm
N
0
0
Alarm ID (ESC exit, TAB next page) : 1
1
DOOR ALARM
Nrm
Y
1
2
D)escription po(L)arity T)rap P)ri.Pager S)ec.Pager (ESC) ?