55
Basic Sensor Configuration
Discover
Resets sensor communication to locate attached sensors.
ID
Sensor ID number.
ROM ID
The ID number found on the sticker of the temperature sensor node. Your Cell16 will
automatically detect the sensor ID when you plug a sensor into the unit. The color of
the sensor ID field will tell you the status of the connected sensor.
Green
- The sensor is connected and properly configured.
Yellow
- The sensor is connected but has not yet been configured (fill in your
configuration fields and click
Save
to configure the sensor).
Red
- The sensor is not detected and configured (i.e. a previous configured sensor is
no longer connected).
Blue
- The sensor is not supported by the Cell16 .
To reconfigure or disable the Sensor ID, simply delete any data in this field and click
Save
.
The unit will refresh the sensor ID on that channel.
Description
User-definable description for the sensor channel.
Notification Devices
Check which notification device(s), 1 through 8, you want to send alarm notifications
for that alarm point.
Advanced Sensor Configuration (Details>>)
Record Freq
The amount of time, in minutes (min) or seconds (s), between each recorded sensor
value.
Deadband
The amount (in native units) that the channel needs to go above or below a threshold
in order to cause an alarm.
On Set
User-definable description (condition) that will appear for the temperature alarm on
Set. Example: "Alarm".
On Clear
User-definable description (condition) that will appear for the temperature alarm Clear.
Example: "Alarm Cleared".
Qual Time (Qualification
Time)
The length of time that must pass, without interruption, in order for the condition to be
considered an Alarm or a Clear.
Qual. Type (Qualification
Type)
Allows you to choose whether you want to apply the Qualification Time to the alarm
Set, Clear, or Both.
Sensor Type
The type of connected sensor.
Note
: The correct sensor type won't display until the Cell16 receives a reading from
the sensor. Before this first reading, sensor type defaults to "Humidity."
Thresholds
These settings are set to indicate the severity of the alarm depending on which
threshold values have been passed. Enter values for Major Under (MjU), Minor Under
(MnU), Minor Over (MnO), and Major Over (MjO).
Analog Gauge Type
Select the color-coded gauge that best represents your data. Selecting
None
will
disable the analog gauge and only a numerical representation of the value will be
displayed under
Monitor
>
Sensors
.
Note:
Before plugging in any additional D-Wire Sensors, set up the internal sensor.