Specifications & Dimensions
Specifications: WNG-2133 BACnet Gateway
BACnet Gateway: Directions & Applications
page 3
lighting controls
Power
Outputs
·
Data signals of either the Douglas MC-6000 Network or
the Douglas W-2000 Network connect to the unit.
·
Output connection from the Douglas Network is activated
by setting the selector switch to that network connection.
·
Douglas W-2000 Network is standard LonTalk
Transceiver, FTT-10 (78kbs) type. Wiring type is twisted
pair, unshielded, #16 AWG Beldon.
·
Douglas MC-6000 Network is RS-485 Transceiver.
Connection is a socket that plugs directly into an
MC-6000 Panel Control Card that has a BACnet encoder.
Programming
·
Use Programming for groups and individual relays in the
Douglas MC-6000 or W-2000 Network is done directly
within the Douglas system interface.
·
BACnet network is allowed up to 1000 points of control
and status for the groups and relays within the
Douglas System.
Environment
·
Indoors, stationary, non-vibrating, non-corrosive
atmosphere and non-condensing humidity.
·
Ambient operating temperature:
0
O
F to +120
0
F (-15
O
to +50
O
C).
Dimensions & Mounting
·
Mount to 35mm
DIN rail installed
in relay panel.
·
24VAC / 100mA Class 2 Low Voltage devices.
Input
·
Input is a BACnet/IP network signal.
·
BACnet/IP connection medium is Ethernet.
·
Communication format is native BACnet/IP.
·
Follow the wiring specifications issued by the host
BACnet system.
Plan View
Side View
Network Technology Specification
·
Network signal:
BACnet IP.
6.5"
(165)
4.0"
(102)
1.75"
(45)
35mm
DIN Rail
Mounting
Power 24VAC
WNG-2133-
BacNet to Douglas Gateway
White
Blue
xx
NE
T
A
Ea
rth
NE
T
B
R
S
-485 B
System
Selector
MC6000 System
W2000 System
R
S
-485 A
LonWorks FTT-10
Data Signal
Service
Wink
This device links external BacNet based system to a
Douglas W-2000 LonWorks based Lighting Control System
or to a Douglas MC-6000 System. The WNG-2133 permits
the external system to switch relay groups, obtain status of
relay groups, switch individual relays and obtain status of
individual relays. The programming of relay groups is done
within the Douglas system using the Douglas user
interface. For detailed information regarding setup and
installation of this device, refer to the WNG-2133
Application Manual.
Self Configured System
WRS-2224: Nodes 24 to 13
WNS-2308: Nodes 8 to 1
Groups: All inherent to the
WRS-2224 and WNS-2308 devices
ü
WNS-2150 Configured System
WRS-2224: Nodes 1-10
Groups: ALL
WRS-2224: Nodes 11-30
Groups: None
WRS-2224: Nodes 31-50
Groups: None
WRS-2224: Nodes 51-70